background image

Harman 300i Wood Insert

11

For Installation In Masonry Fireplace Only

gaskets

Gaskets are used at strategic positions for controlling 

the path that incoming and outgoing air and gases take 

through the insert. You must check these gaskets from 

time  to  time,  and  replace  them  when  necessary. You 

can test the seal by closing the component onto a piece 

of paper. When closed, the paper should not pull out of 

the  seal  without  resistance. The  gaskets  are  made  of 

fiberglass of different sizes (obtainable from your Harman 

dealer) and are fixed in place with a high temperature 

gasket cement. To change a gasket, first remove the worn 

fiberglass  and  clean  the  area  with  a  wire  brush.   Also 

clean any other surfaces that come into contact with the 

gasket. Place a small bead of cement in the area under the 

gasket, then press new gasket material into the channel; 

do not overlap the ends. Seat the gasket firmly by applying 

pressure when possible; for example, after changing the 

door gasket, close the door. Allow the cement to dry before 

using your insert.

Gaskets  are  located  on  the  door  and  between  the 

damper and the damper frame.

door latch

After a period of time, you may find that the front 

door does not close as firmly as when your insert was 

new. This is mostly due to a natural compression of 

the gaskets. To adjust the latch, loosen the two bolts, 

and bump 

the retainer 

back. 

Adjust as 

necessary 

to acheive a 

good seal.

Chimney System

C

reosote Formation And Need For removal 

When wood is burned slowly,  it produces tar and other 

organic  vapors,  which  combine  with  expelled  moisture 

to form creosote. The creosote vapors condense in the 

relatively cool chimney flue of a slow burning fire. As a 

result,  creosote  accumulates  on  the  flue  lining.  When 

ignited, this creosote makes an extremely hot fire.

The FireDome Combustion system cuts creosote to 

almost nothing when properly burned with dry seasoned 

wood.

The  chimney  connector  and  chimney  should  be 

inspected at least once every 2 months during the heating 

season to determine if a creosote buildup has occurred. 

Checking  your  chimney  and  chimney  connector  more 

frequently,  especially  while  you  are  getting  used  to 

your insert, is recommended. To inspect this system, let 

the insert cool. Using a flashlight and mirror, check the 

interior of the chimney connector, and the chimney itself. 

If creosote has accumulated (3mm or more) it should be 

removed to reduce the risk of a chimney fire.

To clean deposits from the surface of the connector, 

open the bypass damper to prevent debris from falling 

into  the  FireDome,  and  clean  using  the  appropriate 

brush. When cleaning the stainless steel connector, it is 

recommended to use a non-metal brush.  

To  clean  the  chimney,  use  a  specially  designed 

brush sized to fit your particular flue opening, or call an 

established chimney cleaning service. It is recommended 

that you have your chimney professionally cleaned and 

inspected  annually. Any  cracks  or  damage  should  be 

repaired before further use of the insert.

Occasionally, it will be necessary to remove the insert 

to  inspect  the  appliance  and  the  fireplace. To  remove 

the insert, you will first need to remove the two bolts that 

secure the flue adapter to the top of the insert. Slide the 

insert out of the fireplace for inspection. Have any cracks 

or damage repaired before further use of the insert.

Do not burn any fuel other than wood, such as charcoal, 

which can cause increased carbon monoxide production 

or overfiring. Never use highly volatile substances in your 

insert, such as gasoline, which could cause an explosion.

When solid fuels are burned completely, they produce 

water and carbon dioxide. However, in long slow burns, a 

substantial amount of carbon monoxide may be produced. 

If allowed to build up, carbon monoxide (which is odorless) 

can prove fatally poisonous. Proper ventilation and draft 

will  prevent  this  from  happening.    If  you  smell  smoke, 

increase  the  air  control  lever  setting,  and  thoroughly 

ventilate your dwelling. During future burns, be careful not 

to overload the insert with fuel, so you will not be tempted 

to constantly operate at a low air control setting.

Other causes of poor draft are icing, exhaust fans, and 

room air starvation, which may occur in tightly constructed 

homes. If your insert is sluggish and you get an occasional 

odor, check these possibilities and increase the air flow in 

your home. Dryer vents and other appliances operating 

in close proximity to the insert may also create negative 

pressure.

Proper ventilation

Always provide a source of  fresh air to the room when 

the insert is operating.

blowers

The  blowers  on  your  insert  require  very  little 

maintenance. You  should,  however,  keep  the  air  inlets 

and the motors and fan blades free of dust and pet hair.

Summary of Contents for 300i

Page 1: ... INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA Contact your local authority such as municipal building department fire department fire prevention bureau etc to determine the need for a permit Cette guide d utilisation est disponible en francais Chez votre concessionnaire de Harman home heating save these in...

Page 2: ......

Page 3: ...claims any responsibility for and the warranty will be voided by the following actions Installation and use of any damaged appliance Modification of the appliance Installation other than as instructed by Hearth Home Technologies Installation of substitute materials or replacement parts not approved by Hearth Home Technologies Operating appliance without fully assembling all components Do NOT Overf...

Page 4: ...RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA Weight 526 lbs Flue Size 6 inch Log Length Recommended 20 Maximum Heating Capacity 1500 to 3000 sq ft Average Emissions 1 1 Grams Per Hr Emissions on Low 0 08 Grams Per Hr Blower Size 2 120 cfm each NOT FOR USE IN MOBILE HOMES 41 1042mm 40 1016mm 28 711mm 17 6 447mm 12 5 318mm 28 5 724mm 5 1 129mm 17 6 447mm 30 762mm 23 75 603mm He...

Page 5: ...au passage d une cheminée à travers un mur ou un plafond combustible Le tuyau de raccord à la cheminée doit être d un diamètre de 15 25 cm 6 po au minimum en acier bleu 24 MSG La cheminée doit être en métal 103HT d usine ou construite en maçonnerie NE RELIEZ PAS CE POÊLE À UNE CHEMINÉE QUI SERT POUR UN AUTRE APPAREIL IL NE FAUT UTILISER QUE DU BOIS EN BUCHES Ne chauffez pas TROP Si l appareil ou l...

Page 6: ...dle upward and pull open to close the door push the door closed and press down on the handle to latch The door must be closed while the insert is in normal operation and the gaskets routinely examined for wear and replaced when necessary Good door seals are important for maintaining control of the insert Operating the insert with the door inadequately sealed could create a serious over firing cond...

Page 7: ... between the glass and the wood This concept helps to keep the glass clean while providing the oxygen needed to sustain burning This is what is known as Primary Combustion Additional air enters at the bottom rear of the stove body Some of this air enters through holes in the rear bricks where it invigorates the fire at the rear of the firebox The remaining air is delivered into the Firedome combus...

Page 8: ... cannot achieve a charcoal bed within the first 15 to 20 minutes your wood is likely too wet and you may need to burn the fire longer and or hotter to compensate for the extra energy needed to drive out the moisture If after five minutes of burning with the damper closed smoke is visible coming from the chimney you probably do not have the proper coal bed Open the bypass damper and continue with t...

Page 9: ...fessionally cleaned and inspected before resuming burning in your insert Always remember to open the bypass damper when you are loading this allows the exhaust gases to pass directly into the flue outlet and reduces the chance of smoke spillage into the room Reloading Once you have prepared and maintained a thick charcoal bed and the secondary combustion is established you should be able to reload...

Page 10: ...n the glass while it is hot and do not use abrasive substances Wash the surface with cool water and rinse thoroughly You may wish to use a nonabrasive cleaner specifically designed for use on stove glass In any case dry thoroughly before relighting your insert Glass Replacement The viewing glass is a specially designed 5 mm ceramic material If the insert s glass is cracked or bro ken you must repl...

Page 11: ...heck the interior of the chimney connector and the chimney itself If creosote has accumulated 3mm or more it should be removed to reduce the risk of a chimney fire To clean deposits from the surface of the connector open the bypass damper to prevent debris from falling into the FireDome and clean using the appropriate brush When cleaning the stainless steel connector it is recommended to use a non...

Page 12: ...e opening to support the insert body Depending on the overall depth of the hearth additional floor protection may be necessary If the depth of the hearth measures 25 5 inches 648 mm or more from the fireplace facing no additional floor protection is needed If the hearth depth is less than 25 5 inches 648 mm floor protection must be installed Floor protection in front of the raised hearth must be a...

Page 13: ...ly 1 4 inch and the roller will disengage when you lower the body It is up to you if you want to raise the roller and lock it in to the disengaged position Lower Base Cover Front Roller Leveling bolt Locked position Ready position Roller Floor Protector Protecteur De Sol Floor protection must ex tend under the insert Never block the air inlets at the front of the insert base 18 457mm 18 457mm 25 5...

Page 14: ...ng the support brackets on each end of the top panel as shown Notice the bottom hole is the one that is threaded Next install the top panel by inserting the four 4 studs through the holes in the fin on the insert Secure with the provided nuts and a 11 32 nut driver Place the top cap down onto the top aligning the two 2 studs with the holes in the top panel Secure from underneath with two 2 nuts In...

Page 15: ...remove the knockout from the surround panel and insert the power cord connectors through it Pull the insulated wire connections from the blower motor and in their place hook up the two female connectors from the cord Next attach the two male connectors from the cord to the insulated wire ends that were removed from the blower Plug the green wire from the power cord into the short green wire that y...

Page 16: ...B365 Canada or NFPA 211 USA Contact your local building authority prior to attempting any clearance reduction From the front of the insert the clearance to combustible materials such as furniture curtains or fuel is 48 inches 1215 mm in the U S and 60 inches 1525 mm in Canada The clearance from the top of the insert to a 12 inch 305mm mantel is 30 inches 762 mm and to facing trim 1 5 inches 38 mm ...

Page 17: ...late Tile Liner Masonry Positive Connect Installation This method is recommended especially if the existing liner is damaged beyond repair or for chimneys that have historically had low draft or smoke spillage problems This stainless steel liner listed to UL 1777 can be rigid or flexible with a chimney cap and top sealing plate or flashing installed Do not mix and match chimney components Use only...

Page 18: ... The bend on the front of the flue bracket and the hooks on the rear will secure the flue collar tightly to the insert When the flue is in its proper position install the two bolts down through the bracket to secure it Handle Installation The door latch handle and the damper handle are left off for shipping and will need to be installed Both handles and their bolts are packaged in the hardware bag...

Page 19: ... Insert 1 70 300100 1 black Ending manufacturing date june 2011 1 70 300100 2 Charcoal 1 70 300100 3 goldenfire 300i 1 2 3 4 5 6 7 8 9 10 12 23 27 22 14 17 16 18 19 21 24 26 25 20 13 11 15 beginning manufacturing date Sept 2010 Ending manufacturing date Active ...

Page 20: ...LD PSA Gasket 10 Ft 1 00 00999 Y 7 Linkage Kit 1 00 300101 Y 8 Damper Arm Cover 2 00 300121P 9 Left Rear Side 2 00 300104B 10 Left Blower Bracket 2 00 300106 1B Screw HWH TEKS 10 X 3 4 Pkg of 100 3 30 5004 100 Y 11 Blower Left Side 3 21 55416 Y 12 Left Side Shield 2 00 300123P Y Screw HWH TEKS 10 X 3 4 Pkg of 100 3 30 5004 100 Y 13 Load Door Latch Assembly 1 00 06903 Includes Screws Steel Sleeve B...

Page 21: ...2 1 00 249153 Y 21 2 Left Plate Assembly w Gasket 1 10 249117A Y Gasket 1 4 Round White Rope 10 Ft 1 00 11862 Y 21 3 Side Brick Brackets 2 Sets 1 00 06945 Y 21 4 Brick Insulation Qty 2 req 3 40 06944 Y 21 5 Brick 12 x 6 x1 4 Qty 4 req 3 40 86125 Y 21 6 Left Side Brick 3 40 00103 Y 21 7 Logo Brick 3 40 00101 Y 21 8 Brick 9 x 4 1 2 x1 1 4 Set of 7 1 00 900450125 Y 21 9 Shoe Brick Gasket 3 44 06951 Y...

Page 22: ...ay be ordered from an authorized dealer Stocked at depot ITEm dESCrIPTION COmmENTS PArT NumbEr 22 Right Side Shield 2 00 300124P Y Screw HWH TEKS 10 X 3 4 Pkg of 100 3 30 5004 100 Y 23 Power Cord w VSC 3 20 300140 Y 24 Right Blower Bracket 2 00 300106 2B Screw HWH TEKS 10 X 3 4 Pkg of 100 3 30 5004 100 Y 25 Right Rear Side 2 00 300105B 26 Blower Right Side 3 21 32080 Y 27 Combustion Package 3 40 0...

Page 23: ...f new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier The warranty shall commence no later than 24 months following the date of product shipment from HHT regardless of the installation or occupancy date The warranty period for parts and ...

Page 24: ...anges in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enameled surfaces caused by fingerprints accidents misuse scratches melted items or other external sources and residues left on the plated surfaces from the use of abrasi...

Page 25: ...ce This powerful heating appliance boasts uncompromising attention to detail and helps preserve our planet by using environmentally responsible fuels Signature of Boxer Your premium quality hearth product designed and assembled by the experienced and skilled members at Harman in Halifax PA USA ...

Reviews: