9
PC 45 Corn/Pellet Stove
Fig. 9
3 ft.
to
combustibles
3 ft.
to
combustibles
venting
#1 Preferred method
This method provides excellent venting for normal
operation and allows the stove to be installed closest
to the wall. Two inches from the wall is safe; however,
four inches allows better access to remove the rear
panel. The vertical portion of the vent should be three
to five feet high. This vertical section will help to provide
natural draft in the event of a power failure.
#2 Preferred method
This method also provides excellent venting for normal
operation but requires the stove to be installed farther
from the wall. The vertical portion of the vent should be
three to five feet high and at least three inches from a
combustible wall. This vertical section will help to pro-
vide natural draft in the event of a power failure.
If the stove is installed below grade the vent termina-
tion should be at least 1 foot above grade.
CAuTION
Keep combustible materials (such as grass, leaves,
etc.) at least 3 feet away from the flue outlet on the
outside of the building.
Fig. 10