P61A Pellet Stove

        

These units are pre-tested at the factory with exactly 

120 Volts A.C., 60 Hz. They are checked and adjusted 

for firebox tightness, gasket leakage, motor operation 

and igniter operation. The P61A is then factory set at a 

mid-point adjustment and in most cases will not need any 

adjustments.  

nOte: the factory low draft setting may 

not be correct for the unit's permanent installation 

conditions.

      The control board on the P61A is equipped with 

a  low  draft  adjustment  port.  Located  on  the  control 

face  just  to  the  right  of  the  igniter  light. This  voltage 

adjustment is provided to allow the unit to be adjusted 

for the household voltage where the unit is going to be 

in permanent operation. 

nOte: the line voltage varies 

from area to area and often home to home.

     The low draft voltage should be adjusted to achieve 

the most efficient burn on low burn or "maintenance". 

This voltage adjustment allows the installer to change 

the low voltage set point approximately 10 volts.  This 

adjustment should be done by the installer during set 

up because a draft meter reading is 

required 

to insure 

proper set up.

       If the unit is not adjusted properly, it does not cause 

a safety concern. If the unit is adjusted too high, only 

efficiency is lost. If the unit is adjusted too low, the low 

draft pressure switch will not allow the feed motor or the 

igniter to operate.

C o m b u s t i o n 

Motor  Speed 

Control

Low  draft  only 

set point.

The small straight 

screwdriver slot is 

plastic; therefore,  

the  unit  can  be 

adjusted while in 

operation.

Fig.22

Fig. 2

 

A  simple  draft  test  should  be  performed  after 

completing the flue pipe installation. To record the results 

for future reference:

1.  Plug unit into a 120VAC, 60 HZ outlet.

2.  Close the hopper lid, front view door, and the ash pan. 

Neither pellets or a fire are required for this test.

.  With the mode selector in the "OFF" position, turn 

the feed adjuster to "TEST".

.  Record the high draft_____in W.C. (Normal is -.50 

to -.60) The control will be on the High Draft for a total 

of 2 minutes.

5.  After 2 minutes, the combustion motor will go down to 

low draft and the distribution blower will go on high. Allow 

approximately 15 seconds to pass for the combustion 

motor to slow before checking the low draft.

6.  If the low draft is between -.5 and -.5, record the 

reading _____ in W.C.  If the reading is higher, slowly 

turn  the  set  screw  counter-clockwise  until  the  draft 

lowers. If the reading is lower, very slowly turn the set 

screw clockwise until the draft increases.

nOte: the test mode alternates from high to low 

draft  every  60  seconds.  if  more  time  is  needed 

for  draft  adjustment, wait until the  next  low draft 

cycle.

nOte: in some cases, the draft may not go as low 

as -.35 to -.45 even with the set screw completely 

counter-clockwise. ideally, you should just set it as 

low as possible.

 

low  draft  voltage  Adjustment

Draft Meter bolt 

hole location

 

T h e   d r a f t 

test hole is under the 

left rear corner of the 

firebox.

low  draft  voltage  Adjustment

Summary of Contents for P61A

Page 1: ...NSTALLATION IN MOBILE HOMES IF THIS HARMAN STOVE IS NOT PROPERLY INSTALLED A HOUSE FIRE MAY RESULT FOR YOUR SAFETY FOL LOW INSTALLATION DIRECTIONS do not use makeshift compromises CONTACT LOCAL BUILDI...

Page 2: ......

Page 3: ...les instructions du constructeur pour l installation et les consignes de fonctionnement Respecter les r gles de s curit en vigueur dans votre r gion AVERTISSEMENT POUR MOBILE HOMES Ne pas installer d...

Page 4: ...ting 27 Mixing Corn with Pellets 28 Options 30 Wiring Diagram 31 Specifications 31 Warranty 32 Service Parts 34 Division of Hearth Home Technologies Inc 352 Mountain House Road Halifax PA 17032 Table...

Page 5: ...rvice person Periodic cleaning is required throughout the heating seasonandat the end of each winter for the stove to work efficiently See cleaning instruc tions on page 22 Mobile Manufactured Home S...

Page 6: ...rance to combustible materials although some can be installed at 1 clearance Rear Cover Panels Shipping Bolts Note These same holes are used for securing the stove in mobile home installation Fig 1 Th...

Page 7: ...eter The draft meter must have a minimum range of 0 5 Record the first reading Connect flue pipe to stove and be sure all doors and windows in the home are closed Record the second draft reading______...

Page 8: ...0 cm above a gas meter regulator assembly when measured from the horizontal center line of the regulator 1 I The clearance to service regulator vent outlet must be a minimum of 6 feet 1 J The clearanc...

Page 9: ...r levels This air must be replaced with cold air from outdoors which flows into lower levels of the house Vents and chimneys into basements and lower levels of the house can become the conduit for air...

Page 10: ...outlet is more than 12 from the inlet cover The maximum length run of this pipe is 15 feet If a longer run is needed the size must be increased to 3 Inlet cover part number 1 10 08542 should be used t...

Page 11: ...throughs CAUTION Keep combustible materials such as grass leaves etc at least 3 feet away from the flue outlet on the outside of the building 1 Preferred method This method provides excellent venting...

Page 12: ...cleaned 5 Installing into an existing fireplace chimney This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure If the chim...

Page 13: ...e sure to use ap proved pellet vent pipe fittings Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Pipe size should be increased to 4 using th...

Page 14: ...clearances Minimum flue vent configuration It is recommended that outside air be installed with this venting configuration to reduce smoke and creosote smell in the room in the event of power failure...

Page 15: ...pointer is not within off position band except after normal shut down Blinks to indicate errors listed below Indicates power to distribution blower Status light error messages 3 Blinks Indicates that...

Page 16: ...ually shut down When the house cools down the stove will automatically bring the room temperature to the precise temperature you desire In the Room Temperature Mode you can select either Auto or Manua...

Page 17: ...the room is already up to temperature The Stove Tempera ture Mode allows you to have a larger fire and a lower sound level without the distribution blower NOTE During the use of this mode if you keep...

Page 18: ...st fire or you are trying different pellets set the feed adjuster to 4 Fig 17 This is a conservative number and will probably need to be increased After you know a feed rate setting that works well us...

Page 19: ...have a large viewing fire without blowing extra heat into the room During operation with the temperature dial set at 5 or less the distribution fan will not operate A 5 on the temperature dial and a...

Page 20: ...o the burn pot causing excessive smoke on start up 3 The firebox low pressure switch will not allow the auger motor or the igniter element to operate if the view door or the ash pan door are open 4 Ad...

Page 21: ...n Motor Speed Control Low draft only set point The small straight screwdriver slot is plastic therefore the unit can be adjusted while in operation Fig 22 Fig 23 A simple draft test should be performe...

Page 22: ...damaged components The glass in your Harman stove is a special ceramic glass Do not abuse the glass by striking or slamming the door Never burn the appliance if the door glass is cracked or broken Rep...

Page 23: ...uld be retained in the closed container until all cinders have thoroughly cooled It is recommended that the stove is cold and shut down when removing the ash pan 1 Lift the latch handle to open the as...

Page 24: ...ON FIRE AND MAY ULTI MATELY CAUSE A HOUSE FIRE 9 Use a brush to clean the flue being careful not to damage the ESP probe see Fig 30 The flue goes straight through into the vent pipe Fig 27 therefore...

Page 25: ...sulated male female wire connectors These connections between the hot leads the wires inside the burn pot and the cold leads the wires from the control board are always pulled to the rear of the feede...

Page 26: ...igniter Poor draft can be caused by blockage in the exhaust excessive build up on the combustion blower fan blades a failed combustion blower or a door or other opening to the firebox not sealed prope...

Page 27: ...n out cover and air intake 3 Burn pot or heat exchanger tubes may need to be cleaned 4 Combination of all the above 5 6 status blink A 6 blink control board status indication is caused by poor or inco...

Page 28: ...to 2 or 3 Set temperature knob to desired amount Turn mode selector knob onto Room Temp mode After the fire has lit watch that the fuel does not feed too fast that it pushes the red glowing fuel bed...

Page 29: ...29 P61A Pellet Stove This page intentionally left blank...

Page 30: ...oad of pellets The hopper extension adds 70 pounds to the existing hopper capacity allowing you to load 140 pounds of pellets at one time The extension seals to the unit hopper with three latches Some...

Page 31: ...E N O CONTACTS MALE FEMALE CONNECTIONS LT BLUE LT BLUE INSIDE BURNPOT IGNITER ELEMENT WHITE 11 PIN PLUG PART NO 3 89 06504 BLACK RED 11 10 4 WHITE EMPTY BLUE YELLOW WHITE WHITE 7 9 8 6 5 WHITE PLUGGED...

Page 32: ...32 P61A Pellet Stove...

Page 33: ...33 P61A Pellet Stove...

Page 34: ...05801 2 charcoal 1 90 05801 3 goldenfire 1 90 05801 4 Metallic blue 1 90 05801 5 honey glo 1 90 05801 10 Mojave Red 1 90 05801 12 Forest green 1 24 2 3 4 5 8 6 7 9 10 11 12 13 16 15 14 17 18 19 20 21...

Page 35: ...1 Air Intake Damper Assembly 1 10 06 66W 2 2 Air Intake Weldment 1 10 06 61 2 Feeder Weldment 1 10 677150 Y 2 Slide Plate Assembly 1 10 080 7 Y 2 5 Pusher Arm Assembly 1 10 06691 Y 2 6 Feed Cover and...

Page 36: ...Air Intake 1 10 72222 7 Gasket Ultra Air Intake Pkg of 10 677160 10 Y 8 Ultra Feeder Weldment 1 10 72 1 2 Y 9 UL Feeder Pusher Arm 1 10 6771 1W Y 10 Fines Deflector no longer available 2 00 6771 8 10...

Page 37: ...085 S Y 1 Ash Pan 1 10 05800 Y 15 Ash Door Assembly 1 10 0672 S 16 Bolt on Hinge 2 00 06952B 17 Cast Door Frame 00 06800P 18 Glass Panel 0 9501 125 Y 19 Door Handle Assembly Pre 1 5 6 1 00 0870 Y Pos...

Page 38: ...21 Y Fuse 6 Amp Pkg of 5 20 9 7 5 Y Gasket 1 Rope Black W PSA Per Inch Glass 1 00 2 12 Y Gasket 8 Rope White LD Per Inch Ash or Load Door 1 00 00888 Y Gasket Burn Pot Tailpipe Pkg of 5 1 00 07 81 Y Ga...

Page 39: ...39 P61A Pellet Stove Service Maintenance Log Date Of Service Performed By Description Of Service...

Page 40: ...Proudly Printed On 100 Recycled Paper...

Reviews: