6. Installing the Equipment
6.3
Electrical
THE APPLIANCE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL
CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE,
ANSI/NFPA 70, OR THE CANADIAN ELECTRICAL CODE, CSA C22.2, AS APPLICABLE.
IF REQUIRED BY LOCAL REGULATION, A GROUND FAULT CURRENT INTERRUPTER (GFCI)
MUST BE INSTALLED BY A QUALIFIED ELECTRICIAN. WHEN THE EQUIPMENT IS
CONNECTED TO THE SUPPLY, THERE ARE POTENTIALLY DANGEROUS VOLTAGES
PRESENT WITHIN THE ELECTRICAL COMPARTMENT AND THROUGHOUT THE CASE. USE
EXTREME CARE WHEN OPENING THE ELECTRICAL COMPARTMENT ACCESS PANEL. WE
RECOMMEND DISCONNECTING THE BREAKER PRIOR TO OPENING THE ELECTRICAL
COMPARTMENT ACCESS PANEL.
The appliance electrical diagram is located on the inside surface of the right side access panel
WHEN THE OVEN IS PLUGGED IN, THERE ARE POTENTIALLY DANGEROUS VOLTAGES
PRESENT IN THE CONTROL CIRCUITS. DO NOT OPEN THE ELECTRICAL COMPARTMENT
AS POTENTIALLY LETHAL VOLTAGES ARE PRESENT INSIDE.
6.3.1
Cord/Plug Connection
THE ROTISSERIE IS SUPPLIED WITH A 6 FOOT (183 CM) LONG ELECTRICAL CORD. THE
CORD IS EQUIPPED WITH A FOUR-PRONG (GROUNDING) PLUG FOR YOUR PROTECTION
AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INTO A PROPERLY
GROUNDED FOUR-PRONG RECEPTACLE. DO NOT CUT OR REMOVE THE GROUNDING
PRONG FROM THIS PLUG.
TO AVOID STRESSING THE POWER CORD,
INSERT THE PLUG WITH THE CORD DOWN
ONLY (GROUND UP). DO NOT ALTER THE
PLUG IN ANY WAY. IF NECESSARY, HAVE
A QUALIFIED ELECTRICIAN ROTATE THE
FACILITY WALL OUTLET ACCORDINGLY.
6.3.2
Permanent Connection
(For model EL1000-PC only)
FOR A PERMANENT CONNECTION
CONFIGURATION, THE ROTISSERIE MUST
BE HARD-WIRED WITH FLEXIBLE CONDUIT
TO A DESIGNATED ELECTRICAL SUPPLY.
THE SUPPLY MUST CONSIST OF:
208V 3-
PHASE “Y” 60 HZ NO NEUTRAL
GROUND (4 CONDUCTORS).
MAX. POWER: 104KW, MAX. DRAW: 33.3A.
CONDUIT SIZE: 1.0” (25 MM).
REFER TO THE WIRING SPECIFICATIONS IN
FIGURE 6-4 AS WELL AS THE RESTRAINING
CABLE REQUIREMENTS IN FIGURE 6-5 AND
FIGURE 6-6.
BLACK
RED
BLUE
Connection
Procedure:
GREEN Ground to
weld stud, install
with washer and
locknut
BLACK to L1
RED to L2
BLUE to L3
Figure 6-4: Permanent Connection
Figure 6-2:
Cord downward only
Figure 6-3:
Do not alter plug