Hardo OptiLine A1 Series Use And Maintenance Instruction Download Page 5

 

 
 

Strona 

5

 z 

16

 

 

OptiLine 60-*******--- lighting fixtures are also available in a version with safety signs (pictograms). The use of pictograms 
requires the installation of diffusing lenses in accordance with the manufacturer's guidelines. 
 
Table 1 shows the basic parameters of the available pictograms. 
 

Pictogram parameters for the OptiLine 60-*******--- 

Length [mm] 

273 

Width [mm] 

127 

Viewing distance [m] 

24 

Luminance [cd/m

2

≥ 300 

Table 1. Basic information about available pictograms for the OptiLine 60-*******--- 

 
 

 

Figure 2. Example of an OptiLine luminaire with a pictogram 

 

 
The standard set of available pictograms can be found in the catalog card of the OptiLine lighting fixture. 

 

2.2 Ex marking 

 

Depending on the version OptiLine series luminaires are marked with Ex features as follow: 

 

II 3G Ex ec IIC T4 Gc, 

     II 2D Ex tb IIIC T70

˚C Db 

 

The individual symbols means: 

 

Name 

Symbol 

Description 

Explosion protection marking 

 

Compliant with European Directive 2014/34/EU (ATEX) for installation in 
hazardous areas. 

Device group 

II 

Device intended for use in explosive atmospheres other than 
underground mining plants. 

Category of devices 

3G 

The device can be safely operated in explosion hazard Zone 2 of gases, 
vapours and mists of flammable liquids with air. 

2D 

The device can be safely operated in dust explosion Zone 21 or 22. 

Type of protection 

Ex ec 

Protection of equipment with increased safety construction "e". 

Ex mc 

Encapsulation protection. 

Summary of Contents for OptiLine A1 Series

Page 1: ...1 z 16 USE AND MAINTENANCE INSTRUCTION OF LIGHTING FIXTURE OptiLine A1 SERIES Instruction no K 26190 PW 0006 HARDO Czapski i Wsp lnicy Sp j Release date 04 04 2024 ul Spacerowa 5 Issue no 1 3 32 083...

Page 2: ...n 7 5 2 Installation 8 5 3 Electrical connection 10 5 3 1 General requirements 10 5 3 2 Execution of luminaire electrical connections 10 6 WORK IN EMERGENCY MODE 11 6 1 General information 11 6 2 Batt...

Page 3: ...ements of the IECEx system Detailed guidance on potentially explosive atmospheres is given in this document Luminaires are approved for use in both external and internal installations The external hou...

Page 4: ...50Hz In emergency mode they are powered from a built in Ni Cd battery pack ensuring backup in emergency mode of not less than 1 5 hours A detailed description of the possible configurations and their...

Page 5: ...log card of the OptiLine lighting fixture 2 2 Ex marking Depending on the version OptiLine series luminaires are marked with Ex features as follow II 3G Ex ec IIC T4 Gc II 2D Ex tb IIIC T70 C Db The i...

Page 6: ...s a high level of safety and which will not become a source of ignition under normal conditions of use and during expected damage 3 SAFETY 3 1 General precautions DANGER THE EXPLOSION HAZARD CAUSED BY...

Page 7: ...t temperature range is unacceptable and will lead to faster wear and or damage At the same time it causes the loss of the manufacturer s warranty Note The use of a luminaire outside the designated ran...

Page 8: ...the GRP lower body At the place where the nuts are mounted the mounting brackets must be fixed with M8 15 mm bolts and M8 spring washers M8 screws should be tightened with a torque of 9 10 Nm Install...

Page 9: ...Strona 9 z 16 Figure 3 Acceptable mounting position...

Page 10: ...5 4 mm2 for luminaires powered on one side Single core cross section 2 5 4 mm2 for pass through or crossed powered luminaires Outer diameter of the cable 8 17 mm the value depends on the size and type...

Page 11: ...ts for emergency lighting OptiLine luminaires A1 have implemented Built in automatic functional test execution Functional tests last one minute and are performed first 1 hour after the first start nex...

Page 12: ...the capacitance test performed at least once every 52 weeks WARNING ALL REPAIRS INCLUDING REPLACEMENT OF THE LIGHT SOURCE OR BATTERY PACK CAN ONLY BE CARRIED OUT USING ORIGINAL SPARE PARTS AND ONLY BY...

Page 13: ...At least once every 1 months a visual and close inspection of the lighting fixture should be carried out During the visual inspection luminaires do not need to be disconnected from the power source Th...

Page 14: ...OSIVE ATMOSPHERE In accordance with the requirements of local regulations electrical tests related to Measurement of the current consumed by the luminaire Measurement of the condition of the insulatio...

Page 15: ...2 2 Photometric data Photometric data for OptiLine A1 for an ambient temperature of 25 C a bar temperature of 4000K and a colour rendering index CRI 80 are shown in Table 3 Type Luminous flux with AC...

Page 16: ...dimensions of OptiLine luminaires are shown in Figure 5 and Table 5 Figure 5 Basic dimensions of OptiLine luminaires Type L L1 B H OptiLine 60 670 400 173 107 OptiLine 12 1276 800 173 107 Table 5 Bas...

Reviews: