Hardo OptiLine A1 Series Use And Maintenance Instruction Download Page 13

 

 
 

Strona 

13

 z 

16

 

 

05 

Normal operation, charging 

 

---- 

06 

Emergency mode, or power supply leakage 

 

In case of power failure 

– 

connect to the power supply 

Table 2. Possible states of the signalling diode. Each dot corresponds to 256 ms 

 

 

7. 

CLEANING 

 

 

 
WARNING: 

ELECTROSTATIC HAZARD.

 

 

 

Each  luminaire  has  a  warning  plate  reading: 

"WARNING:  ELECTROSTATIC  HAZARD"

.    Dust  and  dust  must  not 

accumulate on the housing surfaces. Cleaning should be carried out with a soft cloth with the addition of an antistatic 
agent  or  suitable  vacuum  cleaners  appropriate  to  the  prevailing  environmental  conditions.  It  is  forbidden  to  use 
chemicals that may damage the luminaire or impair functional properties 

 

8. 

MAINTENANCE  

 

 

WARNING: 

SERVICE  AND  MAINTENANCE  WORK  SHOULD  BE  CARRIED  OUT  IN 

ACCORDANCE WITH THE DETAILED REQUIREMENTS OF PN-EN/IEC 60079-17:2014-05. 
 

 

 

WARNING: 

INSPECTIONS AND MAINTENANCE CAN ONLY BE CARRIED OUT BY TRAINED 

AND  EXPERIENCED  PERSONNEL  IN  ACCORDANCE  WITH  THE  REQUIREMENTS  OF  PN-
EN/IEC 60079-17:2014-05.  
 

 

8.1 Visual and close inspections 

 
At least once every 1 months, a visual and close inspection of the lighting fixture should be carried out. During the 
visual inspection, luminaires do not need to be disconnected from the power source. The scope of the inspection 
should include in particular: 

 

 

Visual verification of the correctness of assembly and possible assembly changes;   

 

Visual check of operation;   

 

Visual inspection of the condition of power cables and their markings; 

 

Visual check of the condition of cable glands; 

 

Visual check of the condition of the PC diffuser and GRP body and gaskets for damages and possible dirt; 

 

Visual check of the status and legibility of information labels; 

 

Cleaning the luminaire housing in accordance with the requirements of paragraph 7. 

 
All  irregularities  identified  shall  be  remedied.  A  detailed  description  and  scope  of  activities  is  included  in  the                       
PN-EN/IEC 60079-17:2014-05 standard. 

 

In addition, at least 1 per month, the status of the indicator diode should be checked in accordance with 
section 6.3. 

8.2 Detailed inspections 

 

At  least  once  every  12  months,  a  visual  inspection  of  lighting  fixtures  should  be  carried  out.  During  the  detailed 
inspection, the luminaire must be disconnected from the power source. 

Summary of Contents for OptiLine A1 Series

Page 1: ...1 z 16 USE AND MAINTENANCE INSTRUCTION OF LIGHTING FIXTURE OptiLine A1 SERIES Instruction no K 26190 PW 0006 HARDO Czapski i Wsp lnicy Sp j Release date 04 04 2024 ul Spacerowa 5 Issue no 1 3 32 083...

Page 2: ...n 7 5 2 Installation 8 5 3 Electrical connection 10 5 3 1 General requirements 10 5 3 2 Execution of luminaire electrical connections 10 6 WORK IN EMERGENCY MODE 11 6 1 General information 11 6 2 Batt...

Page 3: ...ements of the IECEx system Detailed guidance on potentially explosive atmospheres is given in this document Luminaires are approved for use in both external and internal installations The external hou...

Page 4: ...50Hz In emergency mode they are powered from a built in Ni Cd battery pack ensuring backup in emergency mode of not less than 1 5 hours A detailed description of the possible configurations and their...

Page 5: ...log card of the OptiLine lighting fixture 2 2 Ex marking Depending on the version OptiLine series luminaires are marked with Ex features as follow II 3G Ex ec IIC T4 Gc II 2D Ex tb IIIC T70 C Db The i...

Page 6: ...s a high level of safety and which will not become a source of ignition under normal conditions of use and during expected damage 3 SAFETY 3 1 General precautions DANGER THE EXPLOSION HAZARD CAUSED BY...

Page 7: ...t temperature range is unacceptable and will lead to faster wear and or damage At the same time it causes the loss of the manufacturer s warranty Note The use of a luminaire outside the designated ran...

Page 8: ...the GRP lower body At the place where the nuts are mounted the mounting brackets must be fixed with M8 15 mm bolts and M8 spring washers M8 screws should be tightened with a torque of 9 10 Nm Install...

Page 9: ...Strona 9 z 16 Figure 3 Acceptable mounting position...

Page 10: ...5 4 mm2 for luminaires powered on one side Single core cross section 2 5 4 mm2 for pass through or crossed powered luminaires Outer diameter of the cable 8 17 mm the value depends on the size and type...

Page 11: ...ts for emergency lighting OptiLine luminaires A1 have implemented Built in automatic functional test execution Functional tests last one minute and are performed first 1 hour after the first start nex...

Page 12: ...the capacitance test performed at least once every 52 weeks WARNING ALL REPAIRS INCLUDING REPLACEMENT OF THE LIGHT SOURCE OR BATTERY PACK CAN ONLY BE CARRIED OUT USING ORIGINAL SPARE PARTS AND ONLY BY...

Page 13: ...At least once every 1 months a visual and close inspection of the lighting fixture should be carried out During the visual inspection luminaires do not need to be disconnected from the power source Th...

Page 14: ...OSIVE ATMOSPHERE In accordance with the requirements of local regulations electrical tests related to Measurement of the current consumed by the luminaire Measurement of the condition of the insulatio...

Page 15: ...2 2 Photometric data Photometric data for OptiLine A1 for an ambient temperature of 25 C a bar temperature of 4000K and a colour rendering index CRI 80 are shown in Table 3 Type Luminous flux with AC...

Page 16: ...dimensions of OptiLine luminaires are shown in Figure 5 and Table 5 Figure 5 Basic dimensions of OptiLine luminaires Type L L1 B H OptiLine 60 670 400 173 107 OptiLine 12 1276 800 173 107 Table 5 Bas...

Reviews: