Connection diagram
▒ Connection diagram of load terminal (R, U)
Appearance
[Unit : mm]
R
U
·40/55/70A items does not have fuse. (90/110/130A items have fast-acting fuse).
·When connecting terminals, please use crimp connectors and securely
fasten them due to the high current flow.
· Max space for solder less terminal connection is - 40/55/70A : 16 mm
- 90/110/130A : 26 mm
▒ Connection diagram of input signal and power terminal
· Current input : 4 - 20 mA DC (connect no. ① and ⑤)
· Voltage input : 1 - 5 V DC (connect no. ② and ⑤)
· Input power voltage (for control unit) :
100 - 240 V AC (no. ③ and ④)
▒ Connection diagram of signal and alarm terminal
• No. ①, ② and ③ : manual V.R
· Use variable resistor of 10 ㏀
· Control 0 ~ 100 % manually
• No. ④ and ⑥ : RUN/STOP
· Be sure to attach RUN contact while it is operating.
• No. ⑤ and ⑥ : ON/OFF control
· When inputting contact, it is operated with 100% output,
irrespective of other control input.
• No. ⑥ is GND terminal of the circuit.
• No. ⑦, ⑧ and ⑨ : Alarm 1 - Warning
This is a “warning” alarm which implies that there may be a
cause of damage to the product and load. At this moment,
TPR stops the output by itself and “warning” alarm is activated.
· Warning error : Overcurrent, overheated heat sink (85 ℃),
SCR short-circuit, abnormal frequency and power.
• ⑩, ⑪, ⑫: Alarm 2 (Caution)
This is a “caution” alarm which implies there is not a serious
problem, but user needs to check for its system because small
and minor problems cause this alarm. At this moment, the output
of TPR is normally operating but only “caution” alarm is activated.
· Caution error : partial load break, overheated heat (65 ℃)
• Initially ⑦ & ⑧ connect. If alarm 1 is activated, ⑧ & ⑨ will be connected.
• Initially ⑩ & ⑪ connect. If alarm 2 is activated, ⑪ & ⑫ will be connected.
MB0401KE131031
Power REGULATOR
TPR-2SL
Thank you for purchasing HANYOUNG product.
Please check whether the product is the exactly same as you ordered.
Before using the product, please read this instruction manual carefully.
Please keep this manual where you can view at any time
•If you use the product with methods other than specified by the manufacturer, there may be bodily injuries
or property damages.
•Since this product is not designed as a safety device if it is used with systems, machines and equipment
that could lead to a risk of life or property damage, please implement safety devices and protections for
both lives and the applications and plan for preventing accidents.
•To prevent damage or failure of this product, please supply the rated power voltage.
•To prevent electric shock or equipment failure, please do not turn on the power until completing wiring.
•Never disassemble, modify, or repair the product. There is a possibility of malfunction, electric shock,
or a risk of fire.
•Please turn off the power when mounting / dismounting of the product. This is a cause of electric shock,
malfunction, or failure.
Warning
•Since the product operating environment influences the product performance and expected life span,
please avoid using in the following places.
· a place where humidity is high and air flow is inappropriate.
· a place where dust or impurity accumulates, ambient temperature is high and vibration level is high.
· a place where corrosive gas (such as harmful gas, ammonia, etc.) and flammable gas occur.
· a place where there is direct vibration and a large physical impact to the product.
· a place where there is water, oil, chemicals, steam, dust, salt, iron or others (Contamination class 1 or 2).
· a place where excessive amounts of inductive interference and electrostatic and magnetic noise occur.
· a place where heat accumulation occurs due to direct sunlight or radiant heat.
•Please do not wipe this product with organic solvents such as alcohol, benzene and others.
(Please use mild detergent)
•Please make sure to inspect the product if exposed to water since there is a possibility of electric leakage
or a risk of fire.
•Please connect the product and other units after turning off all the power of the product, instruments and units.
•Please make sure that the power control (TPR) is installed perpendicularly.
•Please install the product inside of the control panel and install an exhaust fan onto the top of the control panel.
Caution
28, Gilpa-ro 71beon-gil, Nam-gu, Incheon, Korea
TEL : (82-32)876-4697 FAX : (82-32)876-4696
http://www.hynux.com
HANYOUNGNUX CO.,LTD
HEAD OFFICE
JL.CEMPAKA BLOK F 16 NO.02 DELTA SILICON II INDUSTRIAL PARK
LIPPO CIKARANG CICAU, CIKARANG PUSAT, BEKASI INDONESIA 17550
TEL : 62-21-8911-8120~4 FAX : 62-21-8911-8126
PT. HANYOUNG ELECTRONIC INDONESIA
INDONESIA
FACTORY
INSTRUCTION MANUAL
Safety information
Before using the product, please read the safety information thoroughly and use it properly.Alerts declared in the manual
are classified to Danger, Warning and Caution by their criticality
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury
To prevent electric shock while it is running, put to earth with the fixed screw of the unit and do not touch the radiator
panel since it is very hot. Do not touch or contact the input/output terminals because they cause electric shock.
Danger
Suffix code
Specification
Model
Code
Information
TPR-2SL
Slim type Single phase power regulator
Rated current
040
40 A
055
55 A
070
70 A
090
90 A
110
110 A
130
130 A
Power supply voltage
L
100 - 240 V AC (Low)
H
380 - 440 V AC (High)
※ Please supply 100 – 240 V AC to the control unit of the power controller (thyristor) separately.
Model
Low
TPR-2SL040L TPR-2SL055L TPR-2SL070L TPR-2SL090L TPR-2SL110L TPR-2SL130L
High
TPR-2SL040H TPR-2SL055H TPR-2SL070H TPR-2SL090H TPR-2SL110H TPR-2SL130H
Power supply voltage
100 - 240 V AC (Low)
380 - 440 V AC (High)
Circuit input power
100 - 240 V AC
Power frequency
50 Hz / 60 Hz (Dual usage)
Rated current
40 A
55 A
70 A
90 A
110 A
130 A
Applying load
Resistive load
Control
Input
Current input
4 - 20 ㎃ DC (Impedance : 100 Ω)
Voltage input
1 - 5 V DC
Contact input
ON/OFF
External V.R
External volume (10 ㏀)
Control method
Phase control, Fixed Cycle control, Variable Cycle control, ON/OFF control
Movement type
SOFT START, SOFT UP/DOWN
Output voltage
More than 98% of the power supply voltage (In case of maximum current input)
Cooling method
Natural cooling
Forced cooling
Natural cooling
Forced cooling
Display method
Display by LED
Insulation resistance
Min 100 MΩ (Base on 500 V DC mega)
Output control range
0 ~ 100 %
Dielectric strength
3000 V AC 50/60 Hz for 1 min
Line noise
Noise by noise simulator (3,000 V)
Ambient temperature
0 ~ 40 ℃ (Without Condensation)
Ambient Humidity
30 ~ 85 % RH
Storage temperature
-25 ℃ ~ 70 ℃
Weight
1388 g
1478 g
2820 g
3100 g
H1
H2
70 A (With cooling fan)
191 mm
203 mm
219 (H2)
205 (H1)
TPR-2SL 90A~130A 외형도
186
205
50
85
8
6.5
▒ 40/55/70 A
▒ 90/110/130 A
H1
H2
130 A (With cooling fan)
231.5 mm
245.5 mm