Set value change rate limit (RATE)
█
Select whether to use a channel or not (CHEN)
•Initial value : OFF
•Setting range : 0(0.0) ~ Range maximun / minute
•Description : Set the target value (SV) change per minute.
If set to OFF, it does not work.
If the target value (SV) is changed during operation (RUN),
the slope setting (RATE) is activated.
If AT is executed while slope setting (RATE) is running, RATE is immediately
stopped and automatic calculation is executed with the newly set set value.
①
②
⑤
⑥
⑦
⑪
⑩
⑨
⑧
③
④
①
②
③
④
동작모드
동작모드
셋업모드
█
Select whether to use contact input (DISL)
•Initial value : 0
•Setting range : 0, 1
•Description : Select whether to use the DI function.
0 : DI Not used / 1 : DI Used
①
②
⑤
⑥
⑦
⑪
⑩
⑨
⑧
③
④
①
②
③
④
동작모드
동작모드
셋업모드
•Initial value : CONT
•Setting range : OFF, CONT, MONI
•Description : Select whether or not to use each channel for each memory area
OFF : Specifies an unused channel
(When set to OFF, the channel is not displayed)
CONT : It becomes a general control state
MONI : Display only PV value, no control operation