Before start
Installation
Operation
Screen block diagram
Operating screen
Configuration screen
Specifications
25
Sensor type
Use range
Decimal point range
Use range
Decimal point range
℃
℉
Thermoresistor
(R.T.D)
Pt100
Pt - 0
-200 ~ 640
0
-300 ~ 1180
0
Pt - 1
-200.0 ~ 640.0
1
-300.0 ~ 1180.0
1
Pt - 2
-100.00 ~ 150.00
2
-300.0 ~ 1180.0
1
KPt100
KPt - 0
-200 ~ 500
0
-300 ~ 1000
0
KPt - 1
-200.0 ~ 500.0
1
-300.0 ~ 1000.0
1
KPT - 2 -100.00 ~ 150.00
2
-300.0 ~ 1000.0
1
Thermocouple
(T.C)
K
K - 0
-200 ~ 1370
0
-300 ~ 2500
0
K - 1
-200.0 ~ 1370.0
1
-300 ~ 2500
0
J
-200.0 ~ 1200.0
1
-300 ~ 2300
0
E
-200.0 ~ 1000.0
1
-300 ~ 1800
0
T
-200.0 ~ 400.0
1
-300 ~ 750
0
R
0.0 ~ 1700.0
1
0 ~ 3100
0
B
0.0 ~ 1800.0
1
0 ~ 3300
0
S
0.0 ~ 1700.0
1
0 ~ 3100
0
L
-200.0 ~ 900.0
1
-300 ~ 1300
0
N
-200.0 ~ 1300.0
1
-300 ~ 2400
0
U
-200.0 ~ 400.0
1
-300 ~ 750
0
Wre 5 - 26
0.0 ~ 2300.0
1
0 ~ 4200
0
PL-
II
0.0 ~ 1390.0
1
0 ~ 2500
0
[ Range for the sensor types - RTD, TC ]
Sensor type
DCV input range
Use range
Decimal point range
VDC
-10.00 - 20.00
Decimal point = 0 : -10000 ~ 20000
Decimal point = 1 : -1000.0 ~ 2000.0
Decimal point = 2 : -100.00 ~ 200.00
Decimal point = 3 : -10.000 ~ 20.000
0 ~ 3
0.00 - 100.00
1.00 - 5.00
0.00 - 30.00
[ Basic channel configuration parameter ]
[ Range for the sensor types - DCV ]
Parameter
Initial value
Configuration range
Sensor type
K-1
Refer to the table of the ranges for sensor types
DCV input upper limit
DCV upper limit
Within the DCV sensor range
DCV input lower limit
DCV lower limit
Within the DCV sensor range
Upper limit of the use range
Use range (100 %)
Use range (0 ~ 100 %)
Lower limit of the use range
Use range (0 %)
Use range (0 ~ 100 %)
Decimal point location
1
0, 1, 2, 3
Input filter
0 second
0 ~ 120 seconds
Displayed unit
°C
°C, °F, Ω, V, ㎷, %, user
User
UNITnn
Enter the text (up to 6 characters)
( nn : Channel number )