Hanwei BS03 Operation Manual Download Page 6

BS03 fixed gas detector operation manual 

 

 
 

4. Installation 

4.1 Installation position 

1)

 

For petrol gas, oil gas and alcohol gas etc. which is heavier than the air, 
the position is 0.3m-0.6m higher than the ground.   

2)

 

For  natural  gas,  CH4  etc  which  is  lighter  than  the  air,  the  position  is 
0.5m-2m  higher  than  the  gas  source.  Gas  density  more  than 
0.97kg/CBM, then it's heavier. Gas density less than 0.97kg/CBM, then 
it's lighter. 

3)

 

The  position  should  be  far  away  from  shocking,  shattering,  strong 
electromagnetic  interference.  Around  the  position,  there  should  be  at 
least 0.3m empty place.   

4)

 

The position should be within 1m around the possible gas leakage area, 
such  as  valve,  pipe  connection  point,  gas  outlet  place.  Please  try  to 
install it nearer to the above places, but avoid influencing the working of 
the other equipment. Please avoid the environment of high temperature 
and  humidity.  Also  please  keep  it  from  water  swashing,  oil  and 
mechanical  damage.  Please  also  consider  the  convenience  of 
maintenance and calibration. 

                        

5)

 

For  large  scale  detection,  we  suggest  install  1pc  every  10-12  square 
meters, so as to get the best detection result.   

 
 
 
 

No. 

Name 

No. 

Name 

Protection cover 

Pipe connector 

Decoration 

10 

Display screen 

Lower shell 

11 

Wire connection hole 

Upper shell 

12 

H-alarm LED 

Wire connection hole 

13 

L-alarm LED 

Pipe joint 

14 

Fault / Power LED 

Remote  control  receiving 
window 

15 

Ground nut 

Fixing hole 

 

 

Summary of Contents for BS03

Page 1: ...BS03 Fixed gas detector Operation manual Read this manual carefully before using the device Ver HWWM160617CG...

Page 2: ...wise it will influence the accuracy and shorten the sensor life 8 Please don t paint the sensor parts or detector 9 Only sensor spare parts which are specified for BS03 are allowed to be used 10 It s...

Page 3: ...ION 3 4 1 INSTALLATION POSITION 3 4 2 DIMENSIONS 4 4 3 INSTALLATION METHODS 4 5 WIRE CONNECTION 6 6 OPERATION 8 6 1 LOW ALARM SETTING 9 6 2 HIGH ALARM SETTING 9 6 3 ZERO TRANSLATION 9 6 4 SINGLE POINT...

Page 4: ...n Gas Range Resolution Calibrating gas flow LEL 0 100 LEL 1 LEL 500 50ml min CH4 C3H8 0 100 LEL 1 LEL 500 50ml min CH4 0 5 VOL 0 1 VOL 500 50ml min CO 0 1000PPM 1PPM 200ml min H2S 0 100PPM 1PPM 200ml...

Page 5: ...H alarm Operation Infrared remote control Response time 30s LEL 60s toxic gas Working temperature 40 70 LEL 20 50 toxic Working humidity 95 RH Explosion proof Ex d CT6 Protection IP65 Pressure Limit 8...

Page 6: ...thin 1m around the possible gas leakage area such as valve pipe connection point gas outlet place Please try to install it nearer to the above places but avoid influencing the working of the other equ...

Page 7: ...ace you can fix the detector onto the wall or to the gas pipes Please follow the details as below Method 1 thread butted type fixing method If there are transverse or vertical siphon with G3 4 Screw t...

Page 8: ...thod 2 If the user needs to install the detector onto the wall please choose an appropriate place on the wall according to the detector dimensions Then fix the detector by using 3 pieces of M6 70 bulg...

Page 9: ...e way Then use a cross type screw to screw down the 3 bolts and take off the display PCB 2 Screw down the pipe connector in counter clockwise way Take out the explosion proof pad In turns put 3 line w...

Page 10: ...NO mark function spec 1 L Alarm Low alarm output Switching value 2 L Alarm Low alarm output 3 24V Power input DC24V 25 4 GND Power input 5 Iout Current ouput 4 20mA 6 NC 7 H Alarm High alarm output S...

Page 11: ...firm Cancel and Warning It s forbidden to replace the batteries for the remote control in working area Note Setup Confirm and Cancel are single spring buttons These buttons can only be triggered once...

Page 12: ...to exit to return to the normal status 6 2 High alarm setting In normal status press Setup twice and it displays F 2 Then press Confirm it displays the default high alarm This figure can be adjusted b...

Page 13: ...working status the screen will show F 4 then press Confirm and it will display the default calibration point Press or to change the calibration point to be same with the input gas concentration level...

Page 14: ...ent catalytic sensor s using life is 3 years electrochemical sensor s using life is 2 years When the sensor life is overdue the detection result may be not accurate To replace the sensor please first...

Page 15: ...BS03 fixed gas detector operation manual 12...

Page 16: ...Electrical fault Contact with seller Abnormal connection with controller Wiring fault Check the wiring Electrical fault Contact with seller E 01 Calibration fault recalibrating E 02 Wiring fault conn...

Page 17: ...Attachment 1 Address code settings...

Page 18: ......

Page 19: ......

Page 20: ......

Reviews: