Hanwei BS03 Operation Manual Download Page 12

BS03 fixed gas detector operation manual 

 

Display in different status: 
1)

 

Normal status: Display the detecting result of the gas concentration 

2)

 

Sensor fault status: Screen display “E-02”; yellow LED is on. 

3)

 

High  concentration  protection  status(only  available  for  LEL  type): 
Screen display  “100”, 3 LED lights are all on, electrical current output 
21.3mA. 

4)

 

Low alarm status: red L-ALARM LED light is on 

5)

 

High alarm: red L-ALARM  LED  light  and red  H-ALARM  LED lights 
are on. 

6)

 

Low alarm setting: “F--1” 

7)

 

High alarm setting: “F--2” 

8)

 

Zero calibration: “F--3” 

9)

 

Single point calibration: “F--4” 

10)

 

Factory setting: “F--5”(Unavailable to the customers). 

6.1 Low alarm setting 

In  normal  status,  press  “Setup”  once  and  it  displays  “F-1”.  Press 

“Confirm”, it displays  the default low alarm. This figure can be adjusted by 
pressing  “+”  or  “-”.  After  setting  completed,  press  “Confirm”  to  save  the 
setting. The setting will be  effective  immediately  after  exit. The screen will 
display  “F-1”.  You  can  press  “setup”  to  make  the  other  settings  or  press 
“Cancel” to exit to return to the normal status.   

6.2 High alarm setting 

In normal status, press “Setup” twice and it displays “F-2”. Then press 

“Confirm”, it displays the default high alarm. This figure can be adjusted by 
pressing  “+”  or  “-”.  After  setting  completed,  press  “Confirm”  to  save  the 
setting. The setting will be effective immediately after exit. Then the screen 
will display “F-2”. User can press “setup” to make the other settings or press 
“Cancel” to return to the normal status. 

6.3 Zero translation 

After the detector have  been  used  for  a  long  time,  or  the  detector  was 

put  in  a  new  type  environment,  it  may  not  display  “0”  in  clean  air,  this 
phenomenon  is  called  “zero  drift”,  zero  drift  is  normally  caused  by  big 
change  of  temperature  or  humidity,  and  this  phenomenon  can  be  corrected 
by zero translation. 

Zero  translation  can  do  simple  correction  for  gas  detector,  but 

comparing  with  calibration,  it  cannot  correct  the  sensitivity  deviation  after 
long time use. So in principle, please do zero translation for correction only   
when calibration is not convenient to do, and proceed zero calibration every 
half year even zero translation have been made. 

Zero translation method: after the detector works more than 20 minutes, 

Summary of Contents for BS03

Page 1: ...BS03 Fixed gas detector Operation manual Read this manual carefully before using the device Ver HWWM160617CG...

Page 2: ...wise it will influence the accuracy and shorten the sensor life 8 Please don t paint the sensor parts or detector 9 Only sensor spare parts which are specified for BS03 are allowed to be used 10 It s...

Page 3: ...ION 3 4 1 INSTALLATION POSITION 3 4 2 DIMENSIONS 4 4 3 INSTALLATION METHODS 4 5 WIRE CONNECTION 6 6 OPERATION 8 6 1 LOW ALARM SETTING 9 6 2 HIGH ALARM SETTING 9 6 3 ZERO TRANSLATION 9 6 4 SINGLE POINT...

Page 4: ...n Gas Range Resolution Calibrating gas flow LEL 0 100 LEL 1 LEL 500 50ml min CH4 C3H8 0 100 LEL 1 LEL 500 50ml min CH4 0 5 VOL 0 1 VOL 500 50ml min CO 0 1000PPM 1PPM 200ml min H2S 0 100PPM 1PPM 200ml...

Page 5: ...H alarm Operation Infrared remote control Response time 30s LEL 60s toxic gas Working temperature 40 70 LEL 20 50 toxic Working humidity 95 RH Explosion proof Ex d CT6 Protection IP65 Pressure Limit 8...

Page 6: ...thin 1m around the possible gas leakage area such as valve pipe connection point gas outlet place Please try to install it nearer to the above places but avoid influencing the working of the other equ...

Page 7: ...ace you can fix the detector onto the wall or to the gas pipes Please follow the details as below Method 1 thread butted type fixing method If there are transverse or vertical siphon with G3 4 Screw t...

Page 8: ...thod 2 If the user needs to install the detector onto the wall please choose an appropriate place on the wall according to the detector dimensions Then fix the detector by using 3 pieces of M6 70 bulg...

Page 9: ...e way Then use a cross type screw to screw down the 3 bolts and take off the display PCB 2 Screw down the pipe connector in counter clockwise way Take out the explosion proof pad In turns put 3 line w...

Page 10: ...NO mark function spec 1 L Alarm Low alarm output Switching value 2 L Alarm Low alarm output 3 24V Power input DC24V 25 4 GND Power input 5 Iout Current ouput 4 20mA 6 NC 7 H Alarm High alarm output S...

Page 11: ...firm Cancel and Warning It s forbidden to replace the batteries for the remote control in working area Note Setup Confirm and Cancel are single spring buttons These buttons can only be triggered once...

Page 12: ...to exit to return to the normal status 6 2 High alarm setting In normal status press Setup twice and it displays F 2 Then press Confirm it displays the default high alarm This figure can be adjusted b...

Page 13: ...working status the screen will show F 4 then press Confirm and it will display the default calibration point Press or to change the calibration point to be same with the input gas concentration level...

Page 14: ...ent catalytic sensor s using life is 3 years electrochemical sensor s using life is 2 years When the sensor life is overdue the detection result may be not accurate To replace the sensor please first...

Page 15: ...BS03 fixed gas detector operation manual 12...

Page 16: ...Electrical fault Contact with seller Abnormal connection with controller Wiring fault Check the wiring Electrical fault Contact with seller E 01 Calibration fault recalibrating E 02 Wiring fault conn...

Page 17: ...Attachment 1 Address code settings...

Page 18: ......

Page 19: ......

Page 20: ......

Reviews: