INSTALLATION

Protect pressure-relief valves from dirt and moisture. 
Match capacity on valve nameplate to system document 
as specified by system designer and based upon 
protected vessel size. Mount valve directly at the vapor 
space of pressure vessel or on connecting non-valved 
vapor piping as close to the vessel as possible. (Model 
EZLQ liquid relief valves can be connected where 
liquid is to be expected and relieved to a similar or 
lower pressure, not to exceed the set pressure of the 
relief valve. Generally, the relief valve is piped around 
the isolation valve of the protected section or vessel). 
EZ-SRV™ Cartridge pressure-relief valves should be 
installed upright.

Never expose your face or body to a connected relief 
valve exit or piping.

Check that the valve setting and capacity (see Nameplate 
Information Section) meets the requirements per 
system design in accordance with local and national 
regulations. Isolate the valve and related piping from 

the refrigeration system and pump out pressure to zero 
before attempting to install or replace any pressure-
relief valve. Use appropriate safety equipment. Avoid 
residual refrigerant when doing so. A gauge valve and 
gauge can be installed in the inlet pressure port for 
future use to verify and control any refrigerant which 
might remain. See also Gauge Valves and Pressure 

Gauges section on page 6.

Remove shipping caps from the EZ-Fitting. Thread or 
weld EZ-Fitting into the pressure vessel or three-way 
dual shut-off valve at a location in the vapor space 
above the liquid refrigerant level. Install the EZ-SRV™ 
cartridge pressure-relief valve into the EZ-Fitting and 
tighten to approximately 75 foot–lbs (102Nm). These 
valves are for gas relief only. (For liquid relief, Hansen 
offers the EZLQ relief valve specifically designed for 
liquid, refer to page 6). Do not install shut-off valves in 
line with pressure-relief valves. Install valves in locations 
where they will not be damaged by moving equipment 
such as lift trucks, etc. Install valves in a manner that 
enables them to be replaced.

When a dual pressure-relief system is being put into 
service, the three-way valve stem should be positioned 
so that only one valve is exposed to pressure. While 
the three-way valve can be either frontseated (front 
port is closed) or backseated (back port is closed), the 
backseated position is recommended because it takes 
pressure off the packing and reduces the possibility of 
packing leaks.

Vent the relief valve exit to a safe outdoor location in 
an approved manner away from people and building 
openings. Do not install valves or vent piping in a 
refrigerated space unless precautions are taken to 
prevent moisture migration into the valve body or the 
relief vent line. Avoid trapped ice build-up between 
valves and other equipment.

Only apply thread sealing compound to external pipe 

threads and use a modest amount to avoid getting 
compound inside the valve. Use brackets or hangers 
to support the pipe and prevent the valve from being 
overly stressed. Do not put undue stress on the valve 
by using it to stretch or align pipe.

Pressure test all valves and related piping for leaks. 
When testing a dual pressure-relief system, the three-
way valve stem should be in the mid position (only during 
testing), ensuring that all valves are properly leak tested. 
Do not discharge valves prior to installation or when 
pressure testing. Never attempt to reset or change the 
valve setting. Always replace cartridge pressure-relief 
valves once they have discharged.

Hansen EZ-SRV™ valves come with an installation date 
tag to identify the number of years the valve has been 
in service. When installing the EZ-SRV™ valve, remove 
the knockouts corresponding to the current year and 
month. Use a pen to push the knockout partially through 
the tag and tear away from other side.

Pressure-relief valves for ammonia refrigeration are 
subject to preventative inspection and maintenance or 
periodic replacement. Normal replacement is five years 
from installation. However, once a valve discharges it 
must be replaced as soon as possible. Self-reseating is 
not dependable because of the possibility of dirt lodging 
on the seat surface allowing the valve to leak or “weep”.

REPLACING EXISTING RELIEF VALVES

EZ-SRV™ cartridge pressure-relief valves have the 
same capacity as the Hansen H5600 “R” series relief 
valves. The Hansen EZ-Adapter is available to make 
the inlet and outlet connection dimensions the same 
as the Hansen H5600 series. This minimizes piping 
changes to the discharge line connections. The EZ-

Adapter provides the same centerline dimensions as an 

H5600 series relief valve installed with a 2˝ long nipple.  

½˝ EZ-Adapter, p/n 40-0331. ¾˝ EZ-Adapter, p/n 40-0332.

OUTLET

INLET

OUTLET

OUTLET

INLET

OUTLET

Summary of Contents for EZ-SRV Series

Page 1: ...ery five years However if a relief valve has discharged it must be replaced as soon as possible Valve replacement with the Hansen EZ SRV is fast and easy saving significant time and expense compared t...

Page 2: ...ssure relief valve will vent to atmosphere excessive overpressure After discharge these valves will quickly reseat to minimize loss of refrigerant After discharge relief valves must be replaced as soo...

Page 3: ...ies section of this bulletin Example To determine the minimum required capacity of a relief valve for a vessel containing ammonia that measures 16 feet 4 9 m in length and 6 feet 1 8 m in outside diam...

Page 4: ...ront port is closed or backseated back port is closed the backseated position is recommended because it takes pressure off the packing and reduces the possibility of packing leaks Vent the relief valv...

Page 5: ...Air Capacity Pressure Size Set I n l e t Cat No O u t l e t HANSEN TECHNOLOGIES U S A CORPORATION EZ FITTING CONNECTIONS DN BT1 BW1 1 2 x 3 4 15 x 20 BT2 BW2 3 4 x 1 20 x 25 BT4 BW4 1 x 1 1 4 25 x 32...

Page 6: ...te on pressure differential Set points are low differentials of 50 75 and 100 psid The equipment the liquid relief valve is protecting must be designed for a pressure greater than the sum of the desig...

Page 7: ...re use with plated coupling EZ SRV shown with Three Way Shut off Valve and optional Rupture Discs Gauge Valves and Pressure Gauges THREE WAY DUAL SHUT OFF VALVES SHOWN BACKSEATED OUTLET OPEN OUTLET CL...

Page 8: ...tory May require extra delivery time To Order Specify Catalog Number Pressure Setting Optional H7771 Gauge Valve and HG27 Pressure Gauge EZ Adapter if needed and accessories EZ Adapter p n 40 0331 EZ...

Reviews: