background image

Specifications, Applications,

Service Instructions & Parts

EZ-SRV™ CARTRIDGE 

PRESSURE-RELIEF VALVES

Bulletin K129e

JAN 2014

For Ammonia and Halocarbon 

Refrigeration Systems

EZ-SRV™ 

Cartridge Pressure-Relief Valve with EZ-Fitting

INTRODUCTION

Hansen EZ-SRV™ cartridge pressure-relief valves protect 
refrigeration pressure vessels and other refrigeration 
system components from excessive pressure. If an 
abnormally high pressure occurs, the cartridge pressure-
relief valve will open to relieve the excess pressure, 
preventing potential damage to equipment and injury 
to personnel.

Hansen EZ-SRV™ relief valves are built in strict 
conformance with both ASME Boiler and Pressure Vessel 
Code requirements and ISO 4126 — Safety Devices for 
Protection of Excessive Pressure. Each valve bears the 

ASME code symbol of certification (UV).  Valve capacities 

are rated by the National Board of Boiler and Pressure 
Vessel Inspectors (NB).

Refrigeration pressure-relief valves are recommended 
for replacement at least every five years. However, if a 
relief valve has discharged, it must be replaced as soon 
as possible. Valve replacement with the Hansen EZ-SRV™ 
is fast and easy — saving significant time and expense 
compared to traditional relief valves.

The cartridge valve can be replaced more safely than 

previously available pressure-relief valves. The Hansen 
EZ-Fitting has a ¼˝ NPT connection on the side of 
the body. A ¼˝ gauge valve installed with a tell-tale 
pressure gauge can indicate overpressure of a valve 
and if pressure is present when servicing, the ¼˝ gauge 
valve can also be used to safely bleed-off residual 
pressure between the three-way manifold valve and 
the EZ-SRV™ valve.

KEY FEATURES

ADDITIONAL FEATURES

Cartridge design allows quick and easy replacement.
Matched capacities to existing Hansen H5600  

“R” series

Low blowdown (15% or less) for gas service
EZ-Fitting is a permanent fixture, available with 

welded or threaded end connections

MPT inlet eliminates need for nipple
EZ-Adapter component available for retrofit of existing 

Hansen relief valves

Liquid Rated Relief Valve (EZLQ) available

 inch

No.

Serial

Air

Capacity

Pressure

Size

Set

I n l e t

Cat. No.

O u t l e t

HANSEN TECHNOLOGIES

U.S.A.

CORPORATION

Summary of Contents for EZ-SRV Series

Page 1: ...ery five years However if a relief valve has discharged it must be replaced as soon as possible Valve replacement with the Hansen EZ SRV is fast and easy saving significant time and expense compared t...

Page 2: ...ssure relief valve will vent to atmosphere excessive overpressure After discharge these valves will quickly reseat to minimize loss of refrigerant After discharge relief valves must be replaced as soo...

Page 3: ...ies section of this bulletin Example To determine the minimum required capacity of a relief valve for a vessel containing ammonia that measures 16 feet 4 9 m in length and 6 feet 1 8 m in outside diam...

Page 4: ...ront port is closed or backseated back port is closed the backseated position is recommended because it takes pressure off the packing and reduces the possibility of packing leaks Vent the relief valv...

Page 5: ...Air Capacity Pressure Size Set I n l e t Cat No O u t l e t HANSEN TECHNOLOGIES U S A CORPORATION EZ FITTING CONNECTIONS DN BT1 BW1 1 2 x 3 4 15 x 20 BT2 BW2 3 4 x 1 20 x 25 BT4 BW4 1 x 1 1 4 25 x 32...

Page 6: ...te on pressure differential Set points are low differentials of 50 75 and 100 psid The equipment the liquid relief valve is protecting must be designed for a pressure greater than the sum of the desig...

Page 7: ...re use with plated coupling EZ SRV shown with Three Way Shut off Valve and optional Rupture Discs Gauge Valves and Pressure Gauges THREE WAY DUAL SHUT OFF VALVES SHOWN BACKSEATED OUTLET OPEN OUTLET CL...

Page 8: ...tory May require extra delivery time To Order Specify Catalog Number Pressure Setting Optional H7771 Gauge Valve and HG27 Pressure Gauge EZ Adapter if needed and accessories EZ Adapter p n 40 0331 EZ...