73

Table A: Guide to maximum stabilised tem-

peratures  recorded  during  site  tests 

Application 

Mixed water

temperature

Shower 

43°C

Washbasin 

43°C 

Bath (44°C fill) 

46°C

Bath (46°C fill) 

48°C

 

The mixed water temperature at terminal fitting should 
never exceed 46ºC.

If  there  is  a  residual  flow  during  the  commissioning  or 
the annual verification (cold water supply isolation test), 
then this is acceptable providing the temperature of the 
water seeping from the valve is no more than 2°C above 
the designated maximum mixed water outlet temperature 
setting of the valve.
Temperature readings should be taken at the normal flow 
rate after allowing for the system to stabilise. 
The sensing part of the thermometer probe must be fully 
submerged in the water that is to be tested.
Any  TMV  that  has  been  adjusted  or  serviced  must  be 
re-commissioned  and  re-tested  in  accordance  with  the 
manufacturers' instructions.

Commissioning  and  in-service 

tests

Commissioning

Purpose

Since the installed supply conditions are likely to be diffe-
rent from those applied in the laboratory tests it is appro-
priate, at commissioning, to carry out some simple checks 
and tests on each mixing valve to provide a performance 
reference point for future in-service tests.

Procedure

1. 

Check that:

a) the designation of the thermostatic mixing valve

matches the intended application

b) the supply pressures are within the range of ope-

rating pressures for the designation of the valve

c) the supply temperatures are within the range per-

mitted for the valve and by guidance information 
on the prevention of legionella etc.

2.

Adjust the temperature of the mixed water in accor-
dance with the manufacturer’s instructions (page 63)
and the requirement of the application and then carry
out the following sequence:

a) record the temperature of the hot and cold water

supplies

b) record the temperature of the mixed water at the

largest draw-off flow rate

c) record the temperature of the mixed water at a

smaller draw-off flow rate, which shall be measu-
red

d) isolate the cold water supply to the mixing valve

and monitor the mixed water temperature

e) record the maximum temperature achieved as a

result of (d) and the final stabilised temperature

NOTE: The final stabilised mixed water temperature 
should not exceed the values in Table A.

f) record the equipment, thermometer etc. used for

the measurements

Summary of Contents for Ecostat S

Page 1: ...22 ZH 24 RU 26 HU Haszn lati tmutat Szerel si tmutat 28 FI K ytt ohje Asennusohje 30 SV Bruksanvisning Monteringsanvisning 32 LT Vartotojo instrukcija Montavimo instrukcijos 34 HR Upute za uporabu Upu...

Page 2: ...e 1 6 MPa 1 MPa 10 bar 147 PSI Hot water temperature max 80 C Recommended hot water temp max 65 C Thermal disinfection max 70 C 4 min Safety against backflow The product is exclusively designed for dr...

Page 3: ...e set Thermostat has not been adjusted Adjust thermostat Hot water temperature too low Increase hot water temperature to 42 C to 65 C Temperature regulation not possible Temperature regulator dirty or...

Page 4: ...60 Montage 3 2 4 1 2 1 2 1 2 6 5 X X 11 1 2 mm...

Page 5: ...61 Montage 9 PuraVida 15775XXX 8 7 1 2 3 Nr 1047 6220 Ar ma tur en fet t Gr ea se S W 2 m m 4 N m SW 3 mm 4 Nm 11 10...

Page 6: ...62 Safety Function Justierung 1 2 S W 3 m m 1 2 3...

Page 7: ...63 Safety Function 2 1 5 6 S W 3 m m 4 N m 7 8 z B 42 C for example 42 C 1 2 3 4 SW 2 mm 4 Nm...

Page 8: ...64 Wartung SW 4 mm 1 2 2 3 4 5 6 SW 24 mm 1 2 3 1 S W 3 m m SW 2 mm 4...

Page 9: ...65 Wartung SW 4 mm 5 Nm 7 8 9 10 11 12 SW 24 mm 15 Nm Nr 1047 6220 Ar ma tur en fet t Gr ea se S W 3 m m 4 N m SW 2 mm 4 Nm 1 2 3 4...

Page 10: ...eti avage atv rt otvoriti pne hape schlie en ferm close chiudere cerrar sluiten lukke fechar zamkn zav t uzavrie bez r s sulkeminen st nga u daryti Zatvaranje kapatmak nchide zapreti sulgege aizv rt z...

Page 11: ...67 Ecostat E 15700000 Ecostat S 15701000 PuraVida15775XXX Metris 31572000 Ma e Durchflussdiagramm...

Page 12: ...m 95037000 96525000 M5x20 98133000 16x2 96451000 96435000 95508000 48x3 98371000 29x3 97669000 38391000 Ecostat S 15701000 97747000 13595000 25 mm 94073000 96551000 96439000 94282000 94074000 96449000...

Page 13: ...96446000 94009000 96454000 M5x55 98793000 145 mm 95037000 96525000 M5x20 98133000 16x2 96451000 96435000 95508000 48x3 98371000 29x3 97669000 11791XXX 95356XXX 94073000 95904000 96439000 94282000 9407...

Page 14: ...plastic bags carefully Keep children well away from the work area Check for hidden pipes and cables in the wall before drilling holes The unit must be mounted on a finished waterproofed wall surface u...

Page 15: ...allowable temperature tolerances inherent in thermo static mixing valves and temperature losses in metal baths It is not a safe bathing temperature for adults or children The British Burns Association...

Page 16: ...72 KEY Isolating valve Reducing valve Mixer Valve Pump Gas Combination Boiler multi point Unvented System pressure balanced Pumped System...

Page 17: ...priate at commissioning to carry out some simple checks and tests on each mixing valve to provide a performance reference point for future in service tests Procedure 1 Check that a the designation of...

Page 18: ...ce of any other instruction or guidance on the means of determining the appropriate frequency of in service testing the following procedure may be used 1 6 to 8 weeks after commissioning carry out the...

Page 19: ...perature of the water can never exceed 43 C To guarantee a smooth running of the thermostatic element it is necessary from time to time to turn the thermostat from total hot to total cold The thermost...

Page 20: ...76 Hansgrohe Auestra e 5 9 D 77761 Schiltach Telefon 49 0 78 36 51 1282 Telefax 49 0 7836 511440 E Mail info hansgrohe com Internet www hansgrohe com 06 2013 9 08420 08...

Reviews: