approximately 5 seconds the thermostat will exit the parameter options and will return back to the default 
temperature display. 

Code 

Description

 

Range

 

Default Value

 

P0 

Heating/Cooling 

C/H

 

P1 

hysteresis

 

0.1-15

 

2

 

P2 

Upper Limit

 

110

 

110 

P3 

Lower Limit

 

-50

 

-50 

P4 

Correction

 

-7.0 ~ 7.0

 

P5 

Delay Start Time

 

0-10 mins

 

P6 

High Temperature Alarm

 

0-110

 

OFF 

 

P0: Cooling or heating parameter: 

The parameter P0 has two settings, C and H. When set to C (default) the relay will energized  when the 
temperature  is reached. Use this setting  (C)  if connecting to  air-conditioning system. When set to H, the 
relay will de-energize when the temperature is reached, i.e. the heating element will cut off. Use this setting 
if controlling a heating device. 

P1: Hysteresis parameter: 

This set how much change in temperature must occur before the relay will change state. For example if set 
to the default 2°C and the trigger temperature has been set to 25°C, it will not de-energize  until the 
temperature falls back below  23°C. Setting this hysteresis helps stop the  thermostat from continually 
triggering when the temperature drifts around the trip temperature. 

P2: Upper limit of the thermostat parameter: 

This parameter limits the maximum trigger temperature that can be set. It can be used as a safety to stop an 
excessively high trigger temperature from accidentally being set by the user. 

P3: Lower limit of the thermostat parameter: 

This parameter limits the minimum trigger temperature that can be set. It can be used as a safety to stop an 
excessively low trigger temperature from accidentally being set by the user. 

P4: Temperature offset compensation parameter: 

Should you find there is a difference between the displayed temperature and the actual temperature  (for 
instance if the temperature probe is on a long run of cable) you can make minor corrections to  the 
temperature reading with this parameter. 

P5: Trigger delay parameter: 

This parameter allows for delaying switching of the relay when the trigger temperature has be reached. The 
parameter can be set in one minute increments up to a maximum of 10 minutes. 

P6: High temperature alarm parameter: 

Setting a value for this parameter will cause the relay to switch off when the temperature reaches this setting. 
The seven segment display will also show '---' to indicate an alarm condition. The relay will not re-energize 
until the temperature falls below this value. The default setting is OFF. 

 

 