Appendix 

 

MODBUS protocol:  

 

Actuator parameters can be set by using the MODBUS (

RTU) protocol. 

 
Standard supported function codes: 

02 (0x02) Read Discrete Inputs 
03 (0x03) Read Holding Registers. 
04 (0x04) Read Input Registers. 
06 (0x06) Write Single Register. 
 

Hanbay function codes: 

100 (0x64) Re-zero the actuator. 
101 (0x65) Close the valve. 
102 (0x66) Open the valve. 

 
 
 
 
 
Actuator memory map: 

 

Address 

(DEC) 

Address (HEX) 

Offset 

Register Name 

Type 

0x0000 

4001 

MaximumSpeed 

Holding registers.  

READ

 and 

WRITE

 

0x0001 

4002 

MaximumPower 

0x0002 

4003 

NumberOfTurns 

0x0003 

4004 

TargetFromRS485Flag  

0x0004 

4005 

InputRangeLow 

0x0005 

4006 

InputRangeHigh 

0x0006 

4007 

OutputRangeLow 

0x0007 

4008 

OutputRangeHigh 

0x0008 

4009 

TargetPosition 

0x0009 

4010 

SignalLostPosition 

10 

0x000A 

4011 

Reserved 

11 

0x000B 

4012 

Reserved 

12 

0x000C 

4013 

Reserved 

13 

0x000D 

4014 

Reserved 

14 

0x000E 

4015 

Reserved 

15 

0x000F 

4016 

Reserved 

16 

0x0010 

4017 

Reserved 

17 

0x0011 

4018 

Reserved 

18 

0x0012 

4019 

Reserved 

19 

0x0013 

4020 

Reserved 

20 

0x0014 

4021 

CurrentPosition 

Input registers. 

READ

 only 

21 

0x0015 

4022 

StatusRegister 

 
 

If you try to use any other function code, the actuator will answer with the exception code 

0x01

 indicating that 

the attempted function code is not supported. 

Summary of Contents for RC AS-1.05 Series

Page 1: ...s pg 3 Operation pg 4 6 DIP Switch pg 4 Recalibration pg 4 Troubleshooting pg 4 Communications parameters pg 5 Speed and Torque details pg 5 6 Appendix pg 7 14 Modbus Protocol pg 7 12 Power settings p...

Page 2: ...ower supply only 6 White 24VDC 5 Black Power Gnd 4 Pink TD A 3 Grey TD B 2 Brown Isolated Input Signal Gnd 1 Blue Isolated Input Signal 4 20mA Connect the power The RCx may be connected to voltages ra...

Page 3: ...the picture above then connect your input signal on pos 3 and 4 as shown below ACTUATOR 1 2 3 4 5 6 P2 4 20mA Signal source user powered TD A TD B SIGNAL GND RCx Internal RES R66 NOTE 1 Usually the ac...

Page 4: ...it one second and then put it back or use the command code 0x64 In both cases you will see the actuator closing the valve very slowly Troubleshooting Upon noticing a problem your first step should alm...

Page 5: ...only limit the maximum speed The faster you set this maximum speed the less torque you can expect at this maximum speed as shown in the tables below NOTE Depending ONLY on the power setting address 0x...

Page 6: ...que values are for valve seating 2 30 3 18 To convert in lbs to Nm divide the in lbs value by 9 Speed and Torque of RCF xxxAS Actuators Maximum Speed Address 0x0000 Time for 1 Turn sec Torque in in lb...

Page 7: ...isters READ and WRITE 1 0x0001 4002 MaximumPower 2 0x0002 4003 NumberOfTurns 3 0x0003 4004 TargetFromRS485Flag 4 0x0004 4005 InputRangeLow 5 0x0005 4006 InputRangeHigh 6 0x0006 4007 OutputRangeLow 7 0...

Page 8: ...em when in the seating mode The actuator will try to reach the speed set by MaximumSpeed If the torque required is too high the actuator will automatically slow down and deliver the maximum available...

Page 9: ...000 in actuator number 23 0x17 0x06 0x0005 0xFDE8 0x 1 byte 1 byte 2 bytes 2 bytes 2 bytes For a detailed explanation of this two registers please see TargetPosition register description Register name...

Page 10: ...valve 5 turns TargetPosition register has to be set to 1500 Register name Address Max Min Def Actuator address Function code Register address Register new value CRC SignalLostPosition 0x0009 InputRan...

Page 11: ...ngeLow 0 OutputRangeHigh 10000 If CurrentPosition equals to 10000 that means the valve is 5 turns opened If CurrentPosition equals to 2000 that means the valve is 1 turns opened Example 2 If the actua...

Page 12: ...to send Actuator address Function code Input address Qty of inputs CRC 0x21 0x02 0x0000 0x0002 0x 1 byte 1 byte 2 bytes 2 bytes 2 bytes Example 2 To read the discrete inputs 4 Stalled closed in actua...

Page 13: ...2 0 0 1 1 0 0 13 0 0 1 1 0 1 14 0 0 1 1 1 0 15 0 0 1 1 1 1 16 0 1 0 0 0 0 17 0 1 0 0 0 1 18 0 1 0 0 1 0 19 0 1 0 0 1 1 20 0 1 0 1 0 0 21 0 1 0 1 0 1 22 0 1 0 1 1 0 23 0 1 0 1 1 1 24 0 1 1 0 0 0 25 0 1...

Page 14: ...nbayinc com Rev 2018 1 1 800 315 4461 hanbaysales hanbayinc com Main Dimensions Desiccant sticks These sticks change colour when exposed to moisture When they change from the original colour blue to p...

Page 15: ...HANBAY Inc User Manual RCx xxxAS 1 05 Page 15 of 15 www hanbayinc com Rev 2018 1 1 800 315 4461 hanbaysales hanbayinc com Part Number Breakdown Serial Number Full Hanbay Part Number...

Reviews: