User Manual RCx-AC-xxxAx-8.09
Page 3 of 17
www.hanbayinc.com | 1 800 315 4461
Rev.2021.11 [email protected]
Once the cable and cable gland are installed, connect the wires to the pins on the terminal block as
indicated here:
Wiring for Non-Explosion Proof actuators
The actuator comes standard with a pre-installed
cable gland and a 10’ cable. Cut the cable to the length
required, then connect according to the following wire color schematic:
Wire color schematic for cable
Pin
Function
6
Pre-wired to transformer
Connect live wire to loose black cable
with crimp connector (see p.4)
5
Pre-wired to transformer
Connect neutral wire to loose white
cable with crimp connector (see p.4)
4
Feedback signal (4-20 mA)*
3
Not connected
2
Isolated
**
input signal gnd.
1
Isolated
** i
nput signal (4-20 mA)
Colour
Function
Red (1)
Live 110-240 VAC (16 AWG)
Black (2)
Neutral 110-240 VAC (16 AWG)
Blue (3)
Ground (16 AWG)
Green (4)
Not connected
Grey (5)
Feedback* signal (20 AWG)
Yellow (6)
Isolated
**
input signal gnd. (20 AWG)
Blue (7)
Isolated
**
input signal 4
…20 mA (20 AWG)
Remove R66 to
convert
from 4…20
mA to 1-5 V input
signal
Terminal
1 2 3 4 5 6
* “feedback” available in RCx-AC-xxxA
F
version only
** “isolated” available in RCx-AC-xxxA
I
and xxxA
F
versions only
* “feedback” available in RCx-AC-xxxA
F
version only
** “isolated” available in RCx-AC-xxxA
I
and xxxA
F
versions only