HAMWORTHY HEATING LTD
45
MILBORNE
500001130/J
8.10.6 Setting low temperature heating circuit functions for compensated (variable) temperature
Parameter Description
Setting
procedure
End user adjustable parameters
P.3
Low temperature circuit set-
point
Set to required operating temperature.
Limited by settings at parameters 23 & 24.
Heating engineer adjustable parameters – code protected
P.22
Low temperature circuit type Set to 1 for compensated flow temperature
P.23
Low temperature circuit
upper limit
Limits the end users set-point adjustment available at parameter
3. Max 70°C
Sets max flow temperature at the minimum external air
temperature set at parameter 37
P.24
Low temperature circuit
lower limit
Limits the end users set-point adjustment available at parameter
3. Min 10°C
Sets min flow temperature at the maximum external air
temperature set at parameter 38
P.26
Low temperature circuit
hysteresis on
Sets the temperature at which the burner will re-start after
reaching set-point at parameter 3.
Eg. For 50°C set-point. Setting to 7 will re-start the burner at 43°C
P.27
High temperature circuit
hysteresis off
Sets the temperature at which the burner will stop after reaching
set-point at parameter 3.
Eg. For 50°C set-point. Setting to 1 will stop the burner at 51°C
P.28
Mixing valve opening period
Set time taken for mixing valve to open from fully closed position.
Eg 5 secs. Max 255 secs
P.29
Mixing valve closing period
Set time taken for mixing valve to close from fully open position.
Eg 7 secs. Max 255 secs
P.30
Mixing valve static period
Set time mixing valve is to remain static after moving. Eg 5 secs.
Max 255 secs
P.37
Compensation curve min
external air temp setting
Set for external air temperature at which the maximum flow
temperature set in parameter 23 is required. Eg -1°C
Also sets external air temperature limits for high temperature
heating circuit
P.38
Compensation curve max
external air temp setting
Set for external air temperature at which the minimum flow
temperature set in parameter 24 is required. Eg +18°C
Also sets external air temperature limits for high temperature
heating circuit
8.10.6.1 Setting heating circuit functions for 0-10v analog input (TEMPERATURE)
P.14
High temperature circuit type Set to 3 for BMS 0-10v temperature based
P.18
High temperature circuit
lower limit
Limits the end users set-point adjustment available at parameter
1. Min 10°C - Max 50°C
P.19
High temperature circuit
hysteresis on
Sets the temperature at which the burner will re-start after
reaching set-point at parameter 1.
Eg.
For 80°C set-point.
Setting to 7 will re-start the burner at 73°C
P.20
High temperature circuit
hysteresis off
Sets the temperature at which the burner will stop after reaching
set-point at parameter 1.
Eg.
For 80°C set-point. Setting to 1 will stop the burner at 81°C
P.26
Low temperature circuit
hysteresis on
As 19 above.
Eg.
For 40°C set-point. Setting to 7 will re-start
the burner at 33°C
P.27
Low temperature circuit
hysteresis off
As 20 above.
Eg.
For 40°C set-point. Setting to 1 will stop the
burner at 41°C
P.24
Low temperature circuit
lower limit
Limits the end users set-point adjustment available at parameter
3. Min 10°C - Max 25°C
P.22
Low temperature circuit type
Set to 3 for BMS 0-10v temp. based Low temperature circuit