HAMWORTHY HEATING LTD
TRIGON SOLAR THERMAL
500001286/A
4
6.0 REMOTE ALARM MODULE AM1 OPERATION
The Remote Alarm Module AM1 is an interface for the
failure signal transmission between Hamworthy Trigon
devices and external applications. It is to be connected to
a the Hamworthy Trigon DeltaSol BS2 or M Solar
Controllers or Trigon WMZ Calorimeter via the VBus.
When the Remote Alarm Module AM1 is operational, the
LED will glow continuously to signal operational
readiness. If the LED does not glow, check the
connections to the device !
The Remote Alarm Module AM1 receives and processes
the Vbus data of the devices connected. In the case of a
failure signal, the integrated Flash-LED flashes and the
AM1 operates a potential-free relay.
The relay can be used to connect an additional signaling
device, or to connect to a building management system
(BMS).
7.0 IMPORTANT NOTICE
The texts and drawings of this manual are correct to the
best of our knowledge. As faults can never be excluded,
please note:
Your own calculations and plans, under consideration of
the current standards & directions should only be basis
for your projects. We do not offer a guarantee for the
completeness of the drawings and texts of this manual—
they only represent some examples. They can only be
used at your own risk. No liability is assumed for
incorrect, incomplete or false information and / or the
resulting damages.
Note
The design and the specifications can be changed
without notice.
The illustrations may differ from the original products.
5.0 ELECTRICAL CONNECTIONS
Terminals of Remote Alarm Module AM1
The Remote Alarm Module AM1 is designed for
simple connection to the Hamworthy Trigon
DeltaSol BS2 or M Solar Controllers or WMZ
Calorimeter via the VBus. An additional power
supply connection is not necessary.
Connect the VBus cable to the terminals marked
“VBus” with either polarity.
To the terminals marked “REL” a load can be
connected with either polarity.
The bus cable can be extended with a two-wire
cable. The cross section of the cable must be at
least 0.5mm
2
and the cable can be extended up to
50m in the case of a single connection.
ATTENTION !
Low Voltage cables must not run together in a cable
conduit with cables carrying a higher
voltage than 50V.
→
Always Route high & low voltage
cables separately !
→
Pay attention to the local
regulations !