Hampshire Controls Corporation
20 Mar. 2021
MPS Operating Manual
Page 10
Configuration Parameter Descriptions
Edit Limits
Menu
1 Low
,
2 Low
, …,
8 Low
Low alarm limit for probes 1 to 8. The maximum number shown will depend on the
system configuration and the value defined by the
# Channels
parameter. The low
limit parameter is defined in the same units as shown in the sensor readings for each
probe.
1 High
,
2 High
, …,
8 High
High alarm limit for probes 1 to 8. The maximum number shown will depend on the
system configuration and the value defined by the
# Channels
parameter. The high
limit parameter is defined in the same units as shown in the sensor readings for each
probe.
Edit Times
Menu
1AlarmDelay
,
2AlarmDelay
, …,
8AlarmDelay
Alarm delay (in minutes) for probes 1 to 8. The maximum number shown will depend on
the system configuration and the value defined by the
# Channels
parameter. This
value defines the delay between the time the probe reading exceeds the alarm limits and
the time the alarm is activated. The range is
0
to
30
, with a default of
0
.
DoorAlmDelay
For units equipped with a single dry-contact input, this parameter specifies the alarm
delay (in minutes) for that function. The range is
0
to
30
, with a default of
10
. This
parameter will not show up unless the
DoorAlarm
parameter is enabled.
RelayDelay
or
1RelayDelay
,
2RelayDelay
, …,
4RelayDelay
Relay delay (in minutes) for a single relay or relays 1 to 4. The maximum number shown
will depend on the system configuration and the values defined by the
# Channels
and
Relay Def
parameters. This value defines the delay between the time the alarm
is activated and the time the relay changes state. Therefore, the time from the probe
reading exceeding the limits to the time the relay changes state is equal to the sum of the
AlarmDelay
and the
RelayDelay
for each probe. The range is
0
to
120
, with
a default of
0
.
Mute
This parameter configures the alarm mute time (in minutes). When the MUTE/MENU
button is pressed during an alarm condition, the beeper will be silenced (periodic chirp
only) until either the alarm condition goes away, or the mute time elapses. The range is
0
to
120
, with a default of
15
.