ASSEMBLY INSTRUCTIONS
4
INSTRUCTIONS DE MONTAGE
H1
PRODUCT SERIES
SÉRIE DE PRODUIT
Main Protective Grounding
When grounding the rack system or enclosure it
is essential that the main protective ground is
connected and secured first with its own nut
before any bonding connections are made on
top. (Figure 2)
Bonding Connection
Protective Earth Ground
Figure 2
2
Side Panels: Attach bonding wire found in
ground kit to a bonding stud on the side panel
using the ring terminal and hardware provided.
Attach opposite end of wire to the nearest PET
on the rack frame.
3
Doors: Attach bonding wire to the door stud
using the same method described previously.
Attach the opposite end to the nearest front
section bonding stud.
Bonding Instructions
Top and Bottom Panels: Remove one clip nut
from the frame along with the corresponding
screw. Replace with thread cutting screw,
ensuring it penetrates both the panel and the
frame.
TOP PET
STUDS
(INTERNAL)
BOTTOM PET
STUDS
(INTERNAL)