If Ti >38

C, when MTV is on, AUX1 is closed and Indoor fan runs at set speed.

If indoor coil temperature sensor is damages, pre-heat time is set for 2 minutes and Indoor fan runs at

set

speed.

2.G.1

Pre-Heat-------TZ-KM-V6.2 C(D) FOR KM4 WITH ELECTRICAL HEATER.

Indoor fan will turned on after the electrical heater is turned on 30S.

2.G.2 Post-Heat -------TZ-KM-V6.2 FOR KM4 WITHOUT ELECTRICAL HEATER.

If Ti > 38

C, when MTV is off, indoor fan remains on at set speed and AUX1 is opened.

If 35

C <= Ti< =38

C, when MTV is off, AUX1 is opened. Indoor fan keeps original state.

If Ti < 35

C, when MTV is off, AUX1 is opened. Indoor fan stops.

If indoor coil temperature sensor is damages, post-heat time is set for 3 minutes with indoor fan

running at set speed.

2.G.2 Post-Heat -------TZ-KM-V6.2 C(D) FOR KM4 WITH ELECTRICAL HEATER.

Indoor fan will turned off after the unit is turned off 20S.

2.G.3

Protection of indoor coil

If Ti >= 75

C, MTV is turned off, indoor fan remains on and AUX1 is opened. Indoor fan at high

speed.

If Ti < 70

C, MTV is turned on, indoor fan remains on and AUX1 is closed. Indoor fan at set speed.

2.H

DEHUMIDIFICATION MODE

If Tr>= 25

C, MTV will be ON for 3 minutes and OFF for 4 minutes.

If 16

C <= Tr< 25

C, MTV will be ON for 3 minutes and OFF for 6 minutes.

If Tr <16

C, MTV will be turned off.

2.I

AUTO HEAT-DEHUMIDIFICATION-COOL MODE

In auto mode, the set temperature of the system is 24

C and the indoor fan runs in auto fan mode.

If Tr <21

C, the unit will operate in heat mode.

If Tr >25

C, the unit will operate in cool mode.

If 21

C≤ Tr ≤25

C, the unit will operate in dehumidification mode.

Once the unit is turned on in auto mode, it will operate in that mode and will not changeover.

If the unit has been turned off for 2 hours, when turning on the unit, it will select the operating mode
depending on the room temperature.

2.J

AUXILIARY CONTACTS

Cool mode (AUX2)

AUX2 is closed when MTV is on (in normal operation). AUX2 is opened when MTV is off or
protection of indoor coil is operating.

Fan mode (AUX1 and AUX2)

Summary of Contents for Cassy Series

Page 1: ...GUIDE TO THE PRODUCTS FOR CASSY SERIES...

Page 2: ...e made from ABS 3 Multiway air supply ensures room temperature much even and comfortable 4 Coil Coil is designed by coil selection software and tested in factory performance test lab to guarantee the...

Page 3: ...lligent high lift condensate water drainage pump can make the water height of 750 mm which makes it more convenient for the setting of drainage pipe and ensures good drainage performance 7 switch prot...

Page 4: ...design 12 Control system flexible control way standard remote handset control wired wall pad and modbus function optional 13 Fresh air from outdoor can be introduced into room which improves the indo...

Page 5: ...set W with wired wall pad T terminal connection 8 A 50Hz motor B 60Hz motor 9 G with group control function M with Modbus function 10 EH20 with 2 kw electric heater 11 CV2 2way cooling coil valve kits...

Page 6: ...16 8 21 5 27 5 32 9 Noise level dB A 37 34 31 39 36 33 41 39 37 44 41 38 43 39 36 45 41 38 46 44 39 48 45 42 50 47 45 52 49 46 Power supply 220V 50Hz Power input W 35 49 58 70 72 94 130 149 183 220 R...

Page 7: ...2 14 9 17 2 23 1 26 28 1 Heating water flow rate LPM 3 0 3 9 4 7 5 2 6 1 6 9 7 9 10 8 12 1 13 3 Noise level dB A 37 34 31 39 36 33 41 39 37 44 41 38 43 39 36 45 41 38 46 44 39 48 45 42 50 47 45 52 49...

Page 8: ...1 22 dry bulb 26 27 wet bulb total capacity sensible capacity total capacity sensible capacity 17 18 82 95 19 94 94 94 100 19 5 100 100 20 106 99 21 22 dry bulb 28 29 wet bulb total capacity sensible...

Page 9: ...ing capacity 97 94 91 87 Correction coefficient table cooling under different inlet water temp inlet water temp 5 6 7 8 cooling capacity 118 109 100 91 inlet water temp 9 10 cooling capacity 81 70 Cor...

Page 10: ...KM4 05 06 08 mounting brackets air vent KM4 10 12 14 panel Drainge outlet...

Page 11: ...ed Reset Clock Timer Set Swing Mode AM PM Time off Time on Network AM PM A A Timer off Button Press the button once the timer off icon will blink Then you press TIMER button to set timer off time by 1...

Page 12: ...you selcted or all slave units when you press Enter Button 21 Timer ON OFF Button 1 Press TIMER button or appears in LCD 2 Press TIME up or down to select TIMER ON or TIMER OFF or SET 3 If TIMER ON o...

Page 13: ...er unit setting parameters are Unit ON OFF Mode Fan Speed Set Temperature Sleep Function and Swing function 2 A 2 SLAVE UNIT FUNCTION The slave unit runs according to master unit parameters Every unit...

Page 14: ...MTV is turned on AUX2 is closed Indoor fan runs at set speed If Tr Ts cool operation is terminated MTV is turned off AUX2 is opened Indoor fan runs at set speed The range of Ts is 16 to 30 C Indoor fa...

Page 15: ...cal heater is kept original state If Ti 45 C Electrical heater is turned off The range of Ts is 16 to 30 C Indoor fan speed can be adjusted for low medium high and auto When turned on MTV requires 30...

Page 16: ...75 C MTV is turned off indoor fan remains on and AUX1 is opened Indoor fan at high speed If Ti 70 C MTV is turned on indoor fan remains on and AUX1 is closed Indoor fan at set speed 2 H DEHUMIDIFICAT...

Page 17: ...rating 2 K SLEEP FUNCTION Sleep function can only be set in cool or heat modes In cool mode after sleep function is set the indoor fan will run at low speed and Ts will increase 2 C during 2 hours In...

Page 18: ...e sleep set t hr Ts Tr 2 L AUTO FAN SPEED In cool mode the auto fan speed will operate as the following diagram L ST ST 2 ST 3 ST 5 Tr Fan speed M H In COOL mode the fan speed cannot change until it h...

Page 19: ...arameters are mode set temperature swing and the fan speed When power supply resumes or the system is switched on again the same operations as previously set will function 2 P MANUAL OPERATION BUTTON...

Page 20: ...p will work When the float switch is closed the drain pump will run continuously for 5 minutes If the float switch is opened for 10 minutes continuously Red yellow and green LED will blink The drain p...

Page 21: ...3 Black Black Blue R e d W h i t e T A2 A1 A2 A1 V L N TB Wall Pad Legend JP0 Short is master Open is slave JP01 Open is with valve Short is without valve JP1 Transformer JP2 Power supply JP3 2 way va...

Page 22: ...ump JP5 Indoor fan JP6 Remote receiver JP7 Stepping motor JP8 Stepping motor JP9 Stepping motor JP10 Stepping motor JP11 Room TEMP sensor JP12 Indoor coil TEMP sensor JP13 Wall pad JP14 Float switch A...

Page 23: ...d Blue Black Black JP3 JP2 J P 1 JP5 HIGH N M LOW Red Red AUX2 MED JP4 M Yellow Green JP01 JP9JP8 JP10 SM3 4 JP0 JP6 JP13 JP11 JP12 White H M L Blue Green Red Yellow SM1 2 JP7 CPU AUX1 White JP14 JP14...

Page 24: ...06 08 with relay 4KW KM4 10 12 14 with relay Model KV Value Direct Way m3 h KV Value m3 h Pressure MPa Connecting Size HV2 HV3 1 6 1 0 25 DN15 CV2 CV3 2 5 1 6 0 15 DN20 1 flexible mounting kits Right...

Page 25: ...urther information No Model Caliber Body Structure Kv Cv Value Closing Pressure MPa 1 HR G2 1 2 1 2 15mm Actuator and valve body fixed together 2 2 2 5 0 20 2 HR G2 3 4 3 4 20mm 3 0 3 5 0 18 3 HR G2 1...

Page 26: ...d Factory Zhejiang Hammer Air Conditioning Co ltd Factory Add West Renmin Rd Cao e Stree Shangyu City Zhejiang Province P R China Oversea sales office Tel 0086 21 61066961 Fax 0086 21 61066961 821 htt...

Reviews: