Due to the gradual introduction of European
Chimney Standards chimneys will be specified
according to their performance designation as
defined in BS EN 1443 that covers the General
Requirements for chimneys. The minimum
performance designation required for use with solid
fuel burning stoves is T450 N2 S D3.

The flue and chimney installation must be carefully
checked by a competent person before fitting the
stove to ensure it is suitable and will work safely.

If the chimney is old (ie built of brick or stone
without a liner) or being opened up for reuse
additional checks and smoke testing as described in
Appendix E of the Approved Document J 2002
Edition should also be carried out to ensure the flue
and chimney are in good operating condition.

Unless the existing flue is in good condition with
suitable access for collection and removal of debris.
If the flue size is more than 225mm (9 inches)
diameter or 200 x 200mm square, a suitable lining of
150mm (6 inches) diameter should be fitted, or if the
flue length is over 5.5 metres one size larger than the
appliance outlet should be fitted. This should be a
double skin stainless steel flexible flue liner that is
independently certified for use with solid fuel.
Details of suitable linings for use with solid fuel are
given in the Official HETAS guide that can be
viewed on their website at www.hetas.co.uk

It is also important that suitable flue pipe
complying with the Building Regulations is used to
connect the stove to the flue in the chimney and that
suitable access is provided into the flue for regular
inspection and sweeping of the flueways.

The installer should comply with the Building
Regulation requirements in respect of providing a
Notice Plate giving details on the chimney, flue
lining, hearth and fireplace installation. Approved
Document J of the Building Regulations for
England and Wales is available from The Stationery
Bookshops and can also be 
viewed at the ODPM website at
www.safety.odpm.gov.uk/bregs/brads.htm

Details on the relevant Building Regulations and
BS British Standards are given in the "General

Precautions" section page 16 of these instructions.
A chimney may comply with the regulations but
still be subject to down draught and similar
problems. A chimney terminating above the ridge
level is generally less likely to suffer such
problems.

Chimneys should be as straight as possible.
Horizontal runs should be avoided except where
the rear outlet of the appliance is used, in which
case the horizontal section should not exceed
150mm (6'') in length.

If the fire appears to be working hard but produces
very little output to the room it is likely that
excessive draw is present in the chimney, and that
heat is being sucked out of the appliance and up the
chimney. If this is the case we recommend the
fitting of a draught stabiliser in preference to a flue
damper, in the interest of safety and efficiency.

We do not recommend the use of a damper when
burning solid fuel.

FOR ALL APPLIANCES

Access for cleaning the flue should be incorporated
in the system other than through the appliance (e.g.
a soot door or access through register plate).
Purpose-made soot doors and inspection lengths
are available from manufacturers of all systems.

Ensure that the whole length of the flue can be
reached from the soot door.

Note: if the appliance is fitted with a draught
stabiliser or if one is fitted to the flue pipe or
chimney in the same room as the appliance, then
the permanent air entry opening (or openings)
should be increased by 300mm

2

for each kW of

rated output.

For advice on flues and chimneys contact;
NACE (National Association of Chimney
Engineer): telephone 0800 0924019
www.nace.org.uk
or
NACS (National Association of Chimney
Sweeps): telephone 01785 811732
www.chimneyworks.co.uk

18

Hereford Wood/Multifuel Stoves

INSTALLATION

Summary of Contents for Hereford

Page 1: ...Hereford Wood Multifuel Stoves Operating Installation Manual PLEASE RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Hereford 7 Flat Multifuel Stove Rev 1 August 2004 Part No AFS1176...

Page 2: ...ned which is why we are so confident in the reliability of our product Should you have any questions about our Hamlet Stoves that are not covered in this manual please contact the local dealer in your...

Page 3: ...sh Removal 12 Over Firing 12 SERVICING Cleaning 12 Annual Maintenance 13 INSTALLATION Page General Precautions 14 Handling 14 Hearth 14 Combustible Materials 14 Firebox Liner Panels 15 Throat Plate In...

Page 4: ...BURNED IN THIS APPLIANCE TO USE THESE FUELS WILL INVALIDATE THE APPLIANCE GUARANTEE IF IN DOUBT CONTACT THE SOLID FUEL ASSOCIATION TELEPHONE NUMBER 0800 600 000 www solidfuel co uk THE USE OF SPARE PA...

Page 5: ...perly installed and operated a house fire may result installation must comply with the Building Regulations and conform to all relevant fire safety standards Arada Ltd produce a variety of appliances...

Page 6: ...cale 4 Flue spigot 5 Hotplate 7 Operating tool 8 Rear liner 9 Side liners Hereford 7 Wood Multifuel Hereford 10 Wood Multifuel 1 1 1 5 1 2 2 1 5 1 Wood and Multifuel Grate 3 Throat plate 6 Ashpan 1 4...

Page 7: ...Centre of Rear Flue Depth from Back to Centre of Flue mm Flue Diameter Weight Packed Kg 1 7 Hereford 7 Flat 8 4 8 2 2 510 486 359 396 121 127 5 48 Hereford 7 Low 1 7 8 4 8 2 2 680 486 359 396 109 127...

Page 8: ...h has an internal sliding plate with slots housed in a cover plate and is located above the fire door Sliding the control knob to the right as far as it will go achieves the fully open position Slidin...

Page 9: ...flat and in contact with the glass Fig 7 Fig 7 Fitting door glass Replace the two retaining clips and nuts Do not over tighten the nuts as damage may occur to the glass Fig 8 Re place the doors carefu...

Page 10: ...himney and the appliance and increase the risk of chimney fire Note If you have sticky tar inside the appliance or chimney your wood is Green or too wet Recommended Reading Wood as Fuel available from...

Page 11: ...use a fire lighter If using a gas poker be sure to remove it immediately the fire is alight When the fire is well alight regulate the burning rate by adjusting the setting on the primary air inlet co...

Page 12: ...order to protect it so de ashing should cease as soon as the first red embers drop into the ash pan Further de ashing will cause heat build up under the grate which will considerably shorten its life...

Page 13: ...shut down period DOOR GLASS The door glass should remain clear during normal daytimeburning Howeverundercertainconditions such as burning at a low rate with damp wood or overnight burning the glass ma...

Page 14: ...H The fire should be installed to stand on a constructional hearth of non combustible materials not less than 125mm 5 thick conforming to Building Regulations Dimensions of the hearth should project a...

Page 15: ...it on top of the side liners The long centre tab on the back edge rests on the rear liners The shorter turn down tabs against the vertical face Note Neither the rear firebox liners nor the side firebo...

Page 16: ...d Multifuel Stoves INSTALLATION Fig 14 They are fitted as follows To fit the interchangeable canopy Fig 10c Remove the front clamps Tilt the canopy as shown in stage 1 Engage the rear clips and pull f...

Page 17: ...fumes from the stove outlet to the outside air To ensure a good updraught it is important that the flue gases are kept warm and that the flue size suits the stove The termination of the outlet at the...

Page 18: ...cument J of the Building Regulations for England and Wales is available from The Stationery Bookshops and can also be viewed at the ODPM website at www safety odpm gov uk bregs brads htm Details on th...

Page 19: ...Hereford Wood Multifuel Stoves 19 INSTALLATION...

Page 20: ...ULATED FLUES TYPICAL METAL INSULATED CHIMNEY SYSTEM TO BE INSTALLED TO THE CHIMNEY MANUFACTURERS INSTRUCTIONS IN COMPLIANCE WITH BUILDING REGULATIONS AND BS7566 PTS 1 4 A is minimum clearance for non...

Page 21: ...ndividual heating systems should be carried out by a qualified heating engineer In many cases your supplier will be able to offer advice and assistance Direct Systems Stainless steel boilers either fa...

Page 22: ...from the expansion tank should be 28mm diameter copper Pipes in unheated spaces must be lagged FINAL CHECK Before handing over the installation to the customer it is strongly recommended that the appl...

Page 23: ...s appliances only c If clay or concrete flue liners used confirm that they are correctly jointed with socket end uppermost and state jointing materials used d If an existing chimney has been refurbish...

Page 24: ...7 Ashpan 8 Flue Spigot Part Description Visual Aid not to scale Hereford 7 Wood Multifuel AFS1177 AFS1020 AFS1168 AFS009 AFS008 AFS050 AFS010 Hereford 10 Wood Multifuel AFS009 AFS058 AFS010 3 Fire Do...

Page 25: ...xings Per Set 18 Airwash Curved Part Description Visual Aid not to scale Hereford 7 Wood Multifuel AFS1078 AFS1070 AFS1179 AFS1095 AFS1010 AFS047 AFS1144 Hereford 10 Wood Multifuel AFS1009 19 Fire doo...

Page 26: ...Manufacturers decision shall be final If your appliance proves to be defective as a result of faulty materials or workmanship during guarantee we will repair or replace it FREE OF CHARGE as long as t...

Page 27: ...s manual please contact your Hamlet retailer Please keep all repair receipts safely Please ensure you have this manual available when an engineer visits as they will complete the service record chart...

Page 28: ...ked it and it s O K Assembled by Checked by Date of Purchase Name and address of supplier Please ensure installer completes INSTALLATION CHECK LIST details on page 23 of this manual If an add in boile...

Reviews: