Connecting to Water Meter
meterwatch Units With Input Connector
Connector Termination
Please skip this section if you purchased the Halytech supplied pulse probe unit.
You will need to source a pulse probe compatible with the relevant water meter.
The meterwatch connector is supplied with meterwatch
Using a fine tipped soldering iron, solder the wires to the appropriate pins on the supplied 8
pin meterwatch connector as per the table below.
You may need to refer to the documentation provided with the pulse probe to identify the
relevant signals.
Use heat shrink over soldered joints to reduce the risk of shorts occurring in the connector.
Pin meterwatch Meter Pulse Probe Signal
1
Meter Input
Pulse output (+)
2
Do Not Use
3
Ground
Pulse Common/Ground (-)
4
Tamper
Input
Tamper output (+)
5
Do Not Use
6
Ground
Tamper Common/Ground (-)
7
Do Not Use
8
Do Not Use
NOTE
: all of the Ground pins are referenced to a common ground.
Running Pulse Probe Unit Cabling
Run pulse probe unit cable from the meter to the meterwatch
unit. Use stainless cable ties to keep the cable in place or run the
cable in a conduit. The connector fits through a 25mm conduit.
Pass the connector through the stainless-steel tamper bracket as
shown here.
(The tamper bracket will be fitted to meterwatch later.)
Plug the connector into the microSpider input (the one with no red ring) and tighten the ¼ turn
locking nut.