4. Set the type of an external control. For instructions, see
.
Value
Description
Alarm
The external control sends alarm indications.
Demand Close
The external control forces the alarm group (zone)
to close.
Demand Open
The external control forces the alarm group (zone)
to open.
5. Set the connector type of an external alarm device.
a. On the row of the external control, select the "Connector" column.
b. In the selection window, select a value, then select "Change".
Value
Description
Normally Open
Normally Open (NO) alarm device
Normally Closed
Normally Closed (NC) alarm device
6. Make sure the connector type of the external fire system connected to the Halton Safe Management 2.0
system is correct. Select the "Connector" column on the row of the external fire alarm, then do as instructed
in the previous step.
Halton Safe Management 2.0 (SM2) - Installation, commissioning, operating, and maintenance guide
31
1.0
All rights reserved ©Halton