Halton HSM Manual Download Page 2

Product models and accessories

• The central unit of Halton Safe HSM control centre can be modularly extended with Halton

Safe Link control units (HSL), to which the fire dampers and smoke detectors are connected.

You can connect 1–4 fire dampers and 1–4 smoke detectors to one Safe Link control unit.

Optionally You can order a special version of Safe Link that can connect 1-12 smoke

detectors but zero fire dampers. The unit’s internal control logic is used in their management.

Fire dampers and smoke detectors can be clustered into as many as 15 groups, enabling the

system to respond to a fire alarm by closing only those fire dampers that are in the affected

fire compartment.

• You can connect up to six Halton Safe Link (HSL) control units to a Halton Safe Power (HSP)

24 V unit.

• You can add a battery pack for the power failure operational in the main control unit.

• The system can be equipped with an optional 3G remote connection that makes all of the

touchscreen’s functions available via a Web browser.

• Smoke detectors for duct or room installation

2

Summary of Contents for HSM

Page 1: ...arm input Enables time controlled external or manual testing of fire damper operation It produces reports on the operation test The Halton Safe HSM shuts off the fans during test operation and in a fi...

Page 2: ...internal control logic is used in their management Fire dampers and smoke detectors can be clustered into as many as 15 groups enabling the system to respond to a fire alarm by closing only those fire...

Page 3: ...Dimensions 3...

Page 4: ...erial Finishing Note Halton Safe HSM Plastic White IP40 Power supply 230VAC 5 7 touchscreen Halton Safe Link HSL Plastic White IP55 polystyrene casing UL94V 0 IEC 695 2 1 Halton Safe Power HSP Plastic...

Page 5: ...onnect 1 4 fire dampers and 1 4 smoke detectors to one Halton Safe Link control unit Halton Safe Power HSP System allowing you to connect up to six Halton Safe Link HSL control units to a transformer...

Page 6: ...Smoke bottle Assembly stand for a duct smoke detector 6...

Page 7: ...Smoke detector duct installation Smoke detector ceiling installation 7...

Page 8: ...specified by the user The system creates a report on the tests carried out indicating the functionality of each fire damper The system is used with a 5 7 graphical touchscreen through which all neces...

Page 9: ...e cabinet The central unit features a 5 7 touchscreen attached to the front panel of the control centre cabinet The control centre can also be installed on top of the I O unit or next to it If necessa...

Page 10: ...tor s contamination passes a certain threshold The alarm does not close the fire dampers Alarm This closes those fire dampers in the smoke detector s use group Short Cut This means that there is a sho...

Page 11: ...s additional service to the Commissioning package Package 2 The Client connects the power cable attaches Halton Link according to the designs and does wiring for the system components Damper locations...

Page 12: ...cut or a fault in the Halton Safe central unit the Halton Safe Linkcontrol units operate independently If a Halton Safe Link control unit loses its 24 VAC operating voltage because of a fire or a powe...

Page 13: ...R Smoke detector room Calectro ST P DA S Test smoke aerosol Calectro RDP 300 ZT Tailored product ETO N No Y Yes Code example HSM D ZT N 13...

Reviews: