Halton HSM Manual Download Page 10

If the central unit is attached on top of the I/O unit, also the metallic spacer plate must be attached

with these screws. When you are attaching the central unit directly to the wall, the space plate is

attached to the wall by drilling. The central unit is secured at the bottom with two screws.

For more information about electrical connections, see the separate user and installation guide.

Servicing and alarms

The Halton Safe control centre (HSM) and Halton Safe Link (HSL) control unit do not need any

special servicing.

The Calectro smoke detectors for duct or ceiling installation issue the following alarms:

Service

= This situation occurs when the detector’s contamination passes

a certain threshold. The alarm does not close the fire dampers.

Alarm

= This closes those fire dampers in the smoke detector’s use group.

Short Cut

= This means that there is a short circuit in the smoke detector’s

cable. This causes the fire dampers in the smoke detector’s use group to close.

Broken line

= This means that the cable to the smoke detector is broken.

The fire dampers in the relevant smoke detector’s use group are closed.

The smoke detectors are cleaned according to instructions provided by Calectro.

Commissioning

Commissioning instructions are available in tab “Documentation” = ‘User guide Halton Saf`’ –

operation and installation instructions’manual, supplied with the product.

Halton supplies its customers with support service for commissioning, in accordance with the

following table. Ask for a quote from Halton Sales.

10

Summary of Contents for HSM

Page 1: ...arm input Enables time controlled external or manual testing of fire damper operation It produces reports on the operation test The Halton Safe HSM shuts off the fans during test operation and in a fi...

Page 2: ...internal control logic is used in their management Fire dampers and smoke detectors can be clustered into as many as 15 groups enabling the system to respond to a fire alarm by closing only those fire...

Page 3: ...Dimensions 3...

Page 4: ...erial Finishing Note Halton Safe HSM Plastic White IP40 Power supply 230VAC 5 7 touchscreen Halton Safe Link HSL Plastic White IP55 polystyrene casing UL94V 0 IEC 695 2 1 Halton Safe Power HSP Plastic...

Page 5: ...onnect 1 4 fire dampers and 1 4 smoke detectors to one Halton Safe Link control unit Halton Safe Power HSP System allowing you to connect up to six Halton Safe Link HSL control units to a transformer...

Page 6: ...Smoke bottle Assembly stand for a duct smoke detector 6...

Page 7: ...Smoke detector duct installation Smoke detector ceiling installation 7...

Page 8: ...specified by the user The system creates a report on the tests carried out indicating the functionality of each fire damper The system is used with a 5 7 graphical touchscreen through which all neces...

Page 9: ...e cabinet The central unit features a 5 7 touchscreen attached to the front panel of the control centre cabinet The control centre can also be installed on top of the I O unit or next to it If necessa...

Page 10: ...tor s contamination passes a certain threshold The alarm does not close the fire dampers Alarm This closes those fire dampers in the smoke detector s use group Short Cut This means that there is a sho...

Page 11: ...s additional service to the Commissioning package Package 2 The Client connects the power cable attaches Halton Link according to the designs and does wiring for the system components Damper locations...

Page 12: ...cut or a fault in the Halton Safe central unit the Halton Safe Linkcontrol units operate independently If a Halton Safe Link control unit loses its 24 VAC operating voltage because of a fire or a powe...

Page 13: ...R Smoke detector room Calectro ST P DA S Test smoke aerosol Calectro RDP 300 ZT Tailored product ETO N No Y Yes Code example HSM D ZT N 13...