Capture Jet

®

  Operation & Maintenance Manual

 

OM-0

05/0520

17/re

v3/EN

INSTALLATION INSTRUCTIONS

1.  Inspect the crating carefully.  If there are signs of damage, call the freight carrier before uncrating the units.     

Carefully uncrate the units.  Check all local codes prior to installation, special requirements may be necessary  

depending on local building material construction. 

 

** Important note **  Do not leave unit (s) exposed to extreme temperatures for an extended period of  
time,  this may cause the  protective PVC coating around the unit (s) to become very difficult to remove

2.  Position the hood near the actual installation site. In case of multiple hoods, check the engineered set of  

 

drawings for locations.  Pay close attention to collar sizes and fire protection layouts, matching the hood systems 

to the correct location shown on the drawings provided.  

 

**Check item numbers on crates / hoods vs. drawing item numbers.

3.  Once the hood is carefully removed from the shipping crate and set in position, the unit is now ready for installa-

tion. If Halton Company has supplied a backsplash assembly, then the splash assembly should be installed first, 

for installation procedures 

(See pg. 5).

4.  Hang the hood using ½” threaded rods (hanging rods by others) by attaching the rods to the hood  through the 

hanger brackets that are fastened to the top of the hood.  Use of turnbuckles with the threaded rod sections will 

make final adjustment easier. Standard hanging height for canopy hoods ranges from 78” minimum to 84” max-

imum from the finished floor to the lower edge of the front of the hood (per local codes having jurisdiction).   

**Noted in installation instructions - (See pg. 6).

 

 

**All typical installations for Capture Jet

®

 series hoods shown on pages 16-24.

5.  If Closure Panels are supplied by Halton (see pg. 9)  for details on the installation.  

6.  For multiple hoods end to end, or back to back (see pg. 8) for Installation of Splice Strips and U-Channels.

7.  For hoods equipped with a supply fire damper, it is very important to make sure that the fire damper is set in an  

open position before connecting the supply duct. 

 

Electrical circuits should be connected according to standard switch panel wiring diagram, shown on (pg. 10).   

Occasionally desired options may require modifications to the standard wiring (for example remote switch panel).  

The modified wiring diagram will be included with the job specific submittal drawings and should be referenced for 

correct field wiring of hood and accessories. 

 

Additional details about the Halton hood wiring are found with the wiring diagram.

8.  Grease filters and grease cups must be installed in place before start-up.

9.  Halton hood come standard with high output, long lasting LED light fixtures.  Optionally incandescent or recessed 

fluorescent fixtures may be ordered.  Please note only install 100 watt maximum light bulbs in incandescent light 

fixtures.  Fluorescent bulbs should be type T8, 36” or 48” long in fluorescent fixtures.  

**Note: Halton does not 

provide bulbs for incandescent or fluorescent lights.

10.  Protect the hood from damage under normal job site conditions, until all work is complete and system is ready  

to be put into operation.

11.  The KCH Capture Jet

®

 Type I Condensate hood is a highly efficient kitchen ventilation hood that removes contami-

nated air and excess heat emitted by cooking equipment and channels excess condensation from the interior of 

the hood to a perimeter gutter system. This hood is designed to help eliminate water dripping from the edges and 

roof of a standard canopy hood when used with heavy steam producing equipment. Perimeter gutters installed 

on all four sides of the hood capture water from the sides of the hood and redirect it to a channel with a 3/4” NPT 

drain connection.  This drain must be field connected to route the collected condensate for disposal.  All local and 

national plumbing codes must be complied with.

Summary of Contents for Capture Jet KCH

Page 1: ...tors Manual for Capture Jet Manual provides Operation Maintenance and Service Instructions Form OM005_CAPTURE JET Date May 2017 Rev2 Capture Jet Hoods KVE SJ SK KVC SJ SK KVW SJ SK KVL KVM KVR KVO AND...

Page 2: ...contractor to see that the system installation is completed in accordance with the project plans and specifications and that it meets all specific requirements of local code officials The local author...

Page 3: ...to end or back to back see pg 8 for Installation of Splice Strips and U Channels 7 For hoods equipped with a supply fire damper it is very important to make sure that the fire damper is set in an open...

Page 4: ...he Capture Jet plenum on top of the hood or mounted in an electrical enclosure The submittal drawings will detail the location of the speed controller s Information regarding the fan and speed control...

Page 5: ...ew through top of flange to wall screw head will not interfere with hood Screw backsplash to wall or attach with adhesive Halton canopy hoods should be installed from 78 min 84 max above the finished...

Page 6: ...e top of the hood using the turnbuckles will make final adjustments easier Hanging height of Canopy hoods should be per local building codes verify with Authority Having Jurisdiction for hanging heigh...

Page 7: ...be attached to supply collar with sheet metal screws or pop rivets and sealed with duct tape Screws or Rivets are not to interfere with the operation of the fire damper if equipped Recommended Exhaust...

Page 8: ...upply plenum Fig 1 Fig 2 U Channel For hood models that are placed back to back as shown in Fig 1 Slide the U Channel A up over the back of the hood systems and secure with sheet metal screws For hood...

Page 9: ...nel and vertical flange on top of hood should line up 2 Hammer clips C over the two vertical flanges 3 Attach panels B to wall using appropriate hardware D 4 Slide front panel A into place 5 Attach pa...

Page 10: ...AT ANY TIME FANS WILL REMAIN ON FOR 15 MIN AFTER EXHAUST FAN SWITCH IS TURNED OFF H TR 15 MIN DELAY OFF TIMER N 1 2 TR 1 3 4 TEMP SENSORS C R1 R1 1 R2 7 8 R2 1 120V ADDITIONAL RELAY NOTE THE USE OF R...

Page 11: ...es in the fire suppression control cabinet Provision is also made for a Make Up Air interlock which can start the Make Up Air fan whenever the exhaust fan is operating This circuit is typically wired...

Page 12: ...NEUTRAL INCOMING CIRCUIT 120 1 60 J BOX J BOX BLACK WHITE BY HALTON FIELD WIRING The KVL external Capture Jet fan has a fire damper in the collar that must be set to open before the fan is attached to...

Page 13: ...ent screw The adjustment screw allows control of the fan and thus the amount of airflow from the Capture Jets 3 The Capture Jet fan should be adjusted to produce 0 25 of positive water column pressure...

Page 14: ...the cooking equipment is in operation to create a thermal plume prior to the air balancer to be able to use theT A B ports For accurate results the balance contractor should receive a copy of the job...

Page 15: ...and down Lift filter out of plenum Tilt top of filter out Lift filter into plenum Push filter in and down Tilt top of filter in Lift filter to the front Slide filter down Remove KFR tool To remove fi...

Page 16: ...andescent or Fluorescent lighting available KSA Filters 78 84 A F F Standard Verify with Authority in project location for min hanging height 16 ga duct work all welded per code Standard top mounted C...

Page 17: ...3 EN Model KVC Typical Installation Filtered MUA unit on the roof 40 min 120 min 16 ga duct work all welded per code Stainless Steel KSA filters Capture Jet air 78 84 A F F 78 Std Make up airflow Veri...

Page 18: ...r restaurant cooking appliances 78 84 A F F 78 Std Side view of typical install Integrated Capture Jet location 40 min S S KSA Filters Exhaust Air LED lights T A B Ports Integrated Capture Jet fan Ver...

Page 19: ...lation Capture Jet fan KSA filters LED lighting T A B Ports Exhaust Air S S Perf Low Velocity Supply Air W 2 Perf Plenum Capture Jet Air W 1 Perf Plenum Supply Air Exhaust Air Supply Air Capture Jet f...

Page 20: ...Model KVL Typical Installation UL listed upblast fan for restaurant cooking appliances 40 min 58 64 A F F Capture Jet fan Stainless Steel KSA filters 16 ga duct work all welded per code Capture Jet ai...

Page 21: ...Maintenance Manual OM 005 052017 rev3 EN Model KVM Typical Installation UL listed upblast fan for restaurant cooking appliances 40 min Capture Jet fan Stainless Steel KSA filters 16 ga duct work all w...

Page 22: ...1 Panels A are placed at the outside ends of the hood at each end of the hood group 2 Align the weld studs on the upper edges of the side skirts with the holes in the lower edge of hood ends and hang...

Page 23: ...lter angle 24 minimum height Model KVR Round and Oval hoods can be shipped in pieces for field assembly If pieces are shipped loose parts will be marked for easy assembly and an Operation and Installa...

Page 24: ...24 Capture Jet Operation Maintenance Manual OM 005 052017 rev3 EN Model KCH Typical Installation...

Page 25: ...p Date Product Serial Numbers Contact Information Contact Name Title Chef Kitchen Mgr Facility Mgr Property Mgr etc Facility Management Company Name if applicable Email Phone Number Cell Number Fax co...

Page 26: ...ied third party No claims for labor charges will be approved for payment if work commences without prior authorization by Halton Purchaser shall pay incurred premium labor charge including overtime we...