Operating Instructions PS27
9
5.
Configuring the Output Signal
The user can configure the PS27's output signal. This can be done in various ways
Output
SW Pos 3
SW Pos 4
Comments
0…10V
on
off
R
Load
> 50k
Ω
2…10V
on
on
R
Load
> 50k
Ω
0…20mA
off
off
max. load 500
Ω
4…20mA
off
on
max. load 500
Ω
The two-wire model must be configured by the manufacturer.
6.
Setting the Measuring Range (Optional)
The transducer with 4 measuring ranges can be adapted to the measuring
assignment in question. The teaching of 4 measuring ranges into the appliance has
been undertaken by the manufacturer. The switches 1 and 2 of SW can be used to
select the measuring range in question before the transducer is switched on.
SW Pos 1
SW Pos2
Measuring
range
off
off
1
on
off
2
off
on
3
on
on
4
The limiting values of the measuring ranges are noted on the nameplate of the PS27.
Display-optional appliances indicate the limiting value of the selected measuring
range for 1.5 seconds after being switched-on. The appliance should be re-zeroed
following any measuring range change-over. This is because the amplification
change-over may produce offset voltages
.
Four-wire:
Two-wire:
Pos1 Pos2
Pos1 Pos2