PU/PI and PS10 Instruction Manual
9
5
Troubleshooting
Error Description
Potential Cause
Corrective Action
no output signal
supply voltage is not
connected
incorrect supply voltage
defective fuse
defective input protection diode
only for DC power:
defective reverse polarity
protection diode
connect correct supply voltage
connect the correct supply voltage
(see rating plate).
replace the SI1 fuse (Wickmann model
TR5 200 mAT)
Send the instrument to the
manufacturer for repair
Send the instrument to the
manufacturer for repair
output signal is
constant, despite
change in pressure
defective output protection
diode
pressure ports reversed
Send the instrument to the
manufacturer for repair
connect pressure as outlined in
section 3. “Mounting”
output signal incorrect
(only for 0...20 mA)
defective output protection
diode
defective pressure
measurement cell
for current output:
• output loadtoo high
for voltage output:
• load resistance too low
current output calibrated
incorrectly
Send the instrument to the
manufacturer for repair
Send the instrument to the
manufacturer for repair
observe maximum output load of 500
observe minimum load resistance
(either 2 k
, 5 k
or 10 k
, depending
on output; see section 6 “Technical
Data”
follow instructions on calibrating the
zero point at a current output of
0…20mA
zero point cannot be
adjusted using P0
defective pressure measurement
cell
Send the instrument to the
manufacturer for repair