background image

7

OVLEREEQ*G  OVLSREEQ*G  OVLESREEQ*G  OVLSEREEQ*G

97882C - (REV. A - 8/04)

5.

Install the frame squarely in wall

 opening with frame

upright edges flush with the finished wall surface. Place

shelf inside frame and line up the (2) holes on each. Insert

loose ends of rods into holes on sides of shelf panel. Using

appropriately sized screws or bolts (not provided), fasten

the shelf and frame to the bottom of wall opening.

Secure the frame sides and top to the wall opening using

(10) 5/16” bolts or screws (not provided).

NOTE:

Be sure that frame is squared in location. Do not

use less than the required screw quantity and

size.

MODEL OVL-EREE

MODEL OVL-SREE

Legend

Item

Description

A

1/4” O.D. Tube - Water Outlet Connection

B

3/8” O.D. Tube - Water Inlet Connection

C

1-1/4” O.D. Waste Tube

D

Electrical Inlet on Chiller

E

Electrical Outlet Location. Additional UL/CSA listed grounded outlet (By others)
required for 115 Volt, 60Hz.

Figure 11 – OVL-II EREE-Q/OVL-II SREE-Q Rough-In Dimensions

Summary of Contents for OVL-II Series

Page 1: ...alled unit for future reference Service to be performed by authorized service personnel only INSTALLER NOTE It is common practice to ground electrical hardware such as telephones computers and other d...

Page 2: ...ex option Bubbler Gasket Strainer Plate S S Strainer Plate A G Drain Gasket Packing Ring Drain Nut Friction Ring Drain Plug S S Drain Plug A G Drain Tube Drain Tube Waste Tube Gasket Slip Nut Regulato...

Page 3: ...E A G Lower Panel OVL II EREE SREE S S Lower Panel OVL II EREE SREE A G Lower Panel OVL II SEREE ESREE S S Lower Panel OVL II SEREE ESREE A G Strainer Supplied with Chiller Union 1 4 Tee 1 4 Poly Tubi...

Page 4: ...up to 150 lbs static load and provide a means for securing the frame assembly in place NOTE Building construction must allow for adequate air flow on both sides and top of remote chiller unit a minimu...

Page 5: ...ith frame upright support edges flush with the finished wall face Secure the frame to the wall through holes with 12 5 16 bolts or screws not provided Tighten securely NOTE Be sure that frame is squar...

Page 6: ...rce the wall opening on all sides to adequately support the water fountain This reinforcement must support up to 150 lbs static load and provide a means for securing the frame assembly in place NOTE B...

Page 7: ...the bottom of wall opening Secure the frame sides and top to the wall opening using 10 5 16 bolts or screws not provided NOTE Be sure that frame is squared in location Do not use less than the requir...

Page 8: ...trainer provided with chiller by pushing it in until it reaches a positive stop approximately 3 4 19mm on the marked chiller inlet port See Figs 17 18 Attach an unplated and deburred copper water inle...

Page 9: ...lower stream height For Electronic sensor units only remove bottom access panel and turn adjustment screw on the regulator Item 14 Figs 25 27 Clockwise adjustment will raise stream height and counter...

Page 10: ...lator Assembly 19 2 20 29 30 31 23 25 27 26 Stream Height Adjustment Sensor Control The sensor has a 2 second delay time If sensor fails to operate valve mechanism or operates erratically check the fo...

Page 11: ...OVLSREEQ G OVLESREEQ G OVLSEREEQ G 97882C REV A 8 04 Figure 23 Push Bar Fountain Assembly Figure 24 Push Bar Fountain Assembly Side View 3 4 16 17 32 5 10 22 6 7 8 9 13 11 8 12 33 See Fig 22 1 See Fig...

Page 12: ...LOCAL DISTRIBUTOR OR VISIT OUR WEBSITE WWW HALSEYTAYLOR COM Figure 25 View of Electronic Sensor Figure 26 View of Solenoid Valve Figure 27 Electronic Sensor Fountain Assembly Side View Connect To Sen...

Reviews: