PAGE 7
98402C (Rev. C - 02/18)
EHWM14FP*A EHWM17FP*A
The freeze resistant package must be mounted on an interior wall in a heated area. The room temperature of the
interior heated area must be 50° F (10° C) or higher. The freeze resistant package may be surface or recessed
mounted. If recess mounted the surface of the cover must be flush with the interior wall surface. The package is
furnished with screws for mounting the cover to the box. If the box is recess mounted, do not fasten the top and bottom
of the cover to the box. Use the holes on the front only.
1. Assemble the operating cable to the fountain bracket. (Fountain should be mounted to exterior wall). The
adjustment nuts should be in the middle of threaded area on the operating cable. See Figure 5. Create a loop in
the cable and thread the free end of the cable through the wall into the freeze resistant box.
2. Connect free end of operating cable to the valve-operating bracket in the freeze resistant box.
3. Remove cable free play by adjusting the jam nuts on the ends of the operating cable. See Figure 6.
4. Connect water line from fountain bubbler into freeze resistant box. The connection to the box uses a quick connect
water fitting. Position the water line, in the fountain, to drain back into interior mounted box. Any water left
standing, in the exterior line, can freeze.
To insert tubing, push tube straight into fitting until it reaches a positive stop. To remove tubing from the fittings,
relieve water pressure, push in on dark gray collar while pulling out on the tubing. See Figure 10.
5. Connect drain and water supply lines to the freeze resistant fountain. Refer to Figure 1 or Figure 3 for component
positions. Inline strainer must be used on the inlet water line. See Figure 9.
Start-up
1. Turn on building water supply and check all connections for leaks. Repair as required.
2. Stream height is factory set at 35 PSI. If stream height needs to be changed adjust the regulator in the freeze
resistant package. Clockwise adjustment raises stream height, counter clockwise adjustment will lower stream.
3. Adjust operating cable as required. Cable system should have a minimal amount of free play to allow for proper
valve operation. If the system is too tight the valve will stay in the on position creating constant water flow. Too
much free play will result in non-operation of the valve with the push-buttons.
4. Note: Water from the drain back tube in the freeze resistant package, will continue to run while the valve is
actuated.
5. After cable system is adjusted properly stuff flexible insulation into any openings between the outside wall and the
interior box.
6. Recheck all connections. If all connections are leak free replace cover(s) on the freeze resistant box(es) and
fountain(s).
FIG. 9
NOTE: WATER FLOW DIRECTION
BUILDING WATER
INLET
SERVICE STOP
(NOT FURNISHED)
1/4" O.D. TUBE
WATER INLET
3/8" O.D. UNPLATED COP-
PER TUBE CONNECT
COLD WATER SUPPLY
TUBE IS SECURED
IN POSITION
SIMPLY PUSH IN
TUBE TO ATTACH
PUSH IN COLLET
TO RELEASE TUBE
PUSHING TUBE IN BEFORE
PULLING IT OUT HELPS TO
RELEASE TUBE
FIG. 10
OPERATION OF QUICK CONNECT FITTINGS