The Following are all accessible at access level 2 and above
SILENCE BUZZER
Silence Buzzer
– Silences the panel buzzer. Buzzer is activated under the following
conditions:
Alarm Buzzer -
➢
Fire condition
Fault Buzzer -
➢
Fault with loop devices
➢
Fault with the loops
➢
Fault with the fire alarm routing equipment or fault warning routing equipment
➢
Fault with alarm devices or circuit
➢
Fault with connected modules, cards and boards
➢
Fault with secondary power supply
➢
Fault with main power supply
ALARMS SILENCE / RESOUND
Available at access level 2 and above
Alarms Silence / Resound
– Used to silence the alarm devices. Toggle function to
resound any silenced alarm devices, if the ALARMS SILENCED indicator is lit. Only alarm devices
configured with the silence-able attribute set shall respond to silence/resound.
PREVIOUS / NEXT (SEVERAL ALARMS)
Previous / Next (Several Alarms)
– Momentary push buttons, used to
scroll thru the LCD display to view the previous / next available entry. The Several Alarms LED will
illuminate when there is more than one zone is in fire or fire/disabled
RESET
Reset
– Returns the FACP to its normal default state, by clearing all fire alarm
conditions, updating the relevant indicators and outputs and clearing the system fault indicator. If
fault conditions are cleared they must be re-established within 20 seconds.