Halma 10BODYGUARDIII User Manual Download Page 5

POWER-UP 
PROCEDURES 

 

1. 

Upon completion of mechanical and electrical installation, apply 12 to 24 V AC / DC +/- 10% to the Bodyguard, with 
the door in the closed position.  The Bodyguard will flash a green LED at a rate of 2 Hz, then it will expire upon a 
successful set-up in the door-closed position.  
 
NOTE:  If applying the Bodyguard to a door control that requires a learn cycle upon powering, it is recommended 

to allow the doors to complete a learn cycle before applying power to the Bodyguard. 

 

2. 

Activate the door to the full open position.  When used with BEA’s lockout relay, the Bodyguard will once again 
flash the green LED and will execute a door-open set-up.  Upon completion of the set-up for the door-open 
position, the doors will begin closing.  Normal operation should resume thereafter.  Proceed with fine-tuning to 
insure compliance with all applicable safety standards (i.e. ANSI A156.10).  If set-up is unsuccessful, refer to the 
Troubleshooting Guide at the end of this Users Guide, and also to the guide located at the end of the respective 
lockout User’s Guide. 
 
HELPFUL HINT: 
 
#1:  Once the sensor is powered up, and completes a setup for the closed door position, activate the door to the 

open position as indicated above.  During this first open cycle, if the sensor does not begin to flash green 
once the door is full open, a data problem is highly likely.  If the door went open and the sensor just stayed 
red, in detection, it probably did not get the correct data signal from the respective lockout module.  As a 
preliminary check to the troubleshooting, be sure to check the following: 

 

a) 

The White wire from the lockout needs to go to terminal 6 at the Bodyguard, AND the Red/White 

striped wire needs to go terminal 7 at the Bodyguard.  If these two wires are swapped, the 
Bodyguard will NOT work correctly. 

 
b) 

Check to ensure that the voltage from the motor (at the red and black wire of the lockout) has at 

least 10 volts DC.  A voltage that is too low may not be recognized by the lockout. 

 
#2:  If the door goes to the open position and a setup is completed successfully, but then the door begins to close 

and immediately recycles open, it is possible that the Bodyguard’s detection of the closing door is causing a 
recycle.  Be sure to check dipswitch 6, if using an LO21B, U, or P: dipswitch #6 on these modules is typically 
ON for applications where the red and the black wire are connected to a motor.  In these applications the 
lockout expects to see a voltage on these wires when the door is in the OPEN position.  Only specific 
applications, such as a Besam Swingmaster MP (with CUP control) may require the switch to be in the OFF 
position.  Additionally, always make sure that the red wire from the lockout goes to the positive leg of the 
motor (or switch) and the black wire goes to the negative leg.  If these wires are backwards, the system will 
NOT work correctly. 

 

NOTE: Always be sure to refer to the applicable lockout User’s Guide for more detailed information. 

 

 

 

DUEL EGREES: 
REDUCING 
CROSS TALK

 

Perform the following set up using BEA’s remote control to reduce cross talk between duel egress applications.  Refer to 
the figure on page 2 to ensure the two Bodyguards are installed with at least 40” of separation when measured between 
the centerline of each sensor. 
 

1. 

Place doors in the hold open position.  Unlock sensor and set open door Pattern Depth to 5 (Medium Pattern).  
This sequence will turn off threshold IR while door is in open position.  This function should be changed on both 
sensors: 

 

  

+

  

  

+

   

   then  

  

+

   

 

 

2. 

The infrared frequency function may need to be changed.  Change frequency on one of the sensors: 

 

  

+

  

  

+

   

   then  

  

+

   

 

 

3. 

Change to a different mode in applications where high gloss floors or multiple doors are installed in vestibules. 

 

 

Change sensor one to: 

 

  

+

   

  

+

   

   then  

  

+

   

 

 

 

Change sensor two to: 

 

  

+

   

  

+

   

   then  

  

+

   

 

 
 

 
 
 

75.5184.09  EN   20110819 

 

Page 5 of 13 

OBSOLETE

Summary of Contents for 10BODYGUARDIII

Page 1: ...iry of existing settings Should the need arise the Bodyguard may also be tuned by means of two sensor mounted buttons contained on the PC Board within the unit With these two buttons the Bodyguard s f...

Page 2: ...ould be mounted above the door on the swing side The Bodyguard shall be mounted flush with the bottom of the automatic door header This is absolutely necessary to allow the detection pattern to reach...

Page 3: ...nal block OR use the cable that is provided for use with the 10 pin connector Picture 10 If wiring the Bodyguard to a BEA module such as an LO 21 or an MC 15 Refer to the schematic for the respective...

Page 4: ...the angle the farther from the door the pattern will be The 0 angle should only be used when the Bodyguard is mounted to a BodyMount block or to a soffett above the door that extends out from the face...

Page 5: ...eck to ensure that the voltage from the motor at the red and black wire of the lockout has at least 10 volts DC A voltage that is too low may not be recognized by the lockout 2 If the door goes to the...

Page 6: ...nctions may be independently adjusted for each door position Sensitivity Pattern Width Pattern Depth 2 The following functions apply to both door closed and door open positions Automatic Learn Time Im...

Page 7: ...FF Interface 1 New Style 2 LO21 Old Style LO21 B K P S U DPHUB MC15 Infrared Frequency Mode Frequency 1 Normal Low 2 Normal High 3 Quiet Low 4 Quiet High See QUIET MODE Number Keys Number keys 0 throu...

Page 8: ...ight Wide 9 Center Narrow See PATTERN WIDTH or DEPTH Pattern Depth 1 Deep Threshold ON 2 Medium Threshold ON open 3 Limited Threshold ON 4 Deep Threshold OFF 5 Medium Threshold OFF closed 6 Limited Th...

Page 9: ...icate the setting of the particular parameter NOTE Pressing PB1 will toggle between the parameters and pressing PB2 will toggle between the range of adjustments for that particular setting Once you ac...

Page 10: ...21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 2...

Page 11: ...sity lighting 4 See problem IV probable cause 3 3 Ensure that no high intensity lighting is in the immediate area of the sensor 1 Ensure that there is no detection occurring at the Bodyguard If the Re...

Page 12: ...R with the use of a hold open switch While the door is open unlock the Bodyguard and press the setup key followed by the number 2 If the sensor goes back to a red LED as opposed to flashing the green...

Page 13: ...do daily inspections and calling out location of cutoff switches to put equipment out of service if a deficiency is noted The equipment should be inspected in accordance with the minimum inspection g...

Reviews: