-26
ROTARY GEAR PUMP
ELECTRONIC FOAM PROPORTIONING SYSTEM
Section
ΙΙ
ΙΙΙΙ
ΙΙ
ΙΙ
: Installation
Hale FoamMaster System Plumbing Diagram with Single Foam Concentrate Tank
BYPASS
VALVE
FOAM INJECTION
HOSE ½ INCH (12 MM)
INSIDE DIAMETER
RATED FOR 500 PSI
(34 BAR) WITH ½
INCH NPT FITTINGS
BYPASS
HOSE
WATERWAY
CHECK
VALVE
FOAM PUMP AND
MOTOR
ASSEMBLY
IN-LINE FOAM STRAINER/
VALVE ASSEMBLY
WATERWAY
CHECK
VALVE
HALE
FOAMMASTER
HPF
FLOWSENSOR
CHECK VALVE
INJECTOR
FITTING
FOAM SOLUTION
DISCHARGE(S)
FIRE
PUMP
FOAM
TANK
FOAM TANK
DRAIN
VALVE
FOAM SUCTION HOSE
¾ INCH (19 MM) INSIDE
DIAMETER CLEAR
RATED AT 23 INCHES
(584 mm) Hg VACUUM
and 50 PSI (3 BAR)
1 INCH NPT x ¾ INCH
NPT BUSHING
¾ INCH NPT x ¾ INCH
HOSE FITTING
¾ INCH NPT x ¾ INCH
HOSE FITTING
FOAM SUCTION HOSE
¾ INCH (19 MM) INSIDE
DIAMETER CLEAR
RATED AT 23 INCHES
(584 mm) Hg VACUUM
and 500 PSI (34 BAR)
IMPORTANT: When Hale FoamMaster system is ordered
without a tank option the installer must provide the
fittings necessary for flushing the foam system to be
NFPA compliant. These components are:
Foam concentrate check valve; prevents water
contamination of foam tank and pressurization of in-
line strainer/valve assembly.
Tee; to connect flush water hose to foam concentrate
hose.
Flush Water Check Valve; prevents foam
contamination of water system.
Flush Water Shutoff Valve
FLUSH WATER SUPPLY HOSE
3
/
8
OR ½ INCH (10 or 12 MM)
OUTSIDE DIAMETER RATED AT
500 PSI (34 BAR)
FOAM
CONCENTRATE
CHECK VALVE
TEE
FLUSH WATER
VALVE
FLUSH WATER
CHECK VALVE