Operating Instructions 

electronic solenoid valve control type 

IFC 30

 

 

 

operating instructions  

 

Ifc30-ba_eng 

Version:  02/2015 

Date:  26.02.2015 

Page: 18 

 

Fault Messages 

 

The fault indication “wire break” is assigned to the disturbed output. This 
indicator will go off when the next non-faulty impulse is received. 

For example:  
The message “wire break” occurs after the output 5 was controlled. After 
controlling the output 6 the LED wire break goes off again. 
From this results that the wire break fault was causes from the solenoid valve 5. 

 

8.1  Causes of fault and elimination 

Messages 

Indication  Causes of Fault 

Elemination 

wire break 

LED red 

This 
indicator 
will go off 
when the 
next non-
faulty 
impulse is 
received 

No output load during the 
control impulse or short-
circuited valve output. 

 

Check the adjusting of the multi-

  position switch (7). The number 
  of connected valves must agree 
  with the adjusting of the multi-
  position switch 

 

Check the valve connection 

 

Check the valve 

 

lack of air 

LED red 

 

The pressure switch input P 
indicates no signal at the end 
of the delay time. 

 

Check the compressed air and 

  the pressure switch 

 

If no monitoring of the 

  compressed air shall be 
  carried out, switch the DIP 
  switches 2 (19) to the OFF 
  position. 

Summary of Contents for IFC 30

Page 1: ... 27798 Hude web www hainke de Operating Instructions electronic solenoid valve control type IFC 30 Driftinstruktion Bedrijfshandleiding Instruções de serviço Instrucciones de servicio Istruzioni per l ésercizio Instruction de service Betriebsanleitung Operating Instructions Electronic Solenoid Valve Control Type IFC 30 ...

Page 2: ...1 1 Designation electrical apparatus for explosion hazardous areas 3 1 2 Operating of the Unit in the add on housing 4 1 3 Remarks for special conditions for safe use 4 2 Use as agreed 4 3 Technical Data 5 4 Installation 7 4 1 Safety notes for the installation general Fehler Textmarke nicht definiert 5 Electrical Connection 10 6 Commissioning 12 7 Control and Signal Functions 15 7 1 Remote Control...

Page 3: ... result in severe personal injury or property damage This equipment may be installed connected commissioned operated and maintained by qualified and authorised personnel only under strict observance of these operating instructions any relevant standards and legal requirements Take particular note of the general and regional installation and safety regulations regarding work on high voltage install...

Page 4: ...up non conductive dust T80 C Maximum surface temperature Dc EPL Equipment Protection Level Dust II 3D X Remarks for special conditions for safe use IP 65 Ingress protection IP 65 Ta 5 C 40 C Permissible operating temperature range Areas of application Equipment Category Explosive dust air mixtures D Category 1 Zone 20 21 or 22 Category 2 Zone 21 or 22 Category 3 Zone 22 not conductive dust Equipme...

Page 5: ...te ATTENTION 1 Permissible operating temperature range Ta 10 C to 40 C 2 The control has to be installed within the visual range and must be protected from any mechanical damage 3 The control must be protected from ultraviolet light daylight or ultraviolet light from lamps respectively be mounted in a protected place 4 Avoid dust deposits on the unit 5 To avoid electrostatic charging clean the uni...

Page 6: ...olenoid valve outputs 24VDC output power max 24W 1A activated manually by means of a multi contact switch All outputs are suppressed with a recovery diode Impulse period Adjustable from 60 to 600 ms indicated by red LED Delay period Adjustable from 6 to 60 s indicated by green LED Post cleaning Selectable from 0 to 5 cycles delay period is automatically reduced Indication by LEDs Red wire breakage...

Page 7: ... x 150 mm Weight 5 6 kg Cable entries 4 x M16 4 x M20 Clamp range of Cable entries M16 for 4 0 to 8 0 mm M20 for 6 5 to 12 0 mm or 10 0 to 14mm Connection cross section 0 2 to 2 5 mm unit marking II 3D T Ex tc IIIB T80 C Dc X IP65 Ta 5 C 40 C Maximum surface temperature T of the housing Category 3D at 40 C ambient temperature 80 C Permissible operating temperature explosion hazardous area zone 22 ...

Page 8: ...n explosion hazardous area Ex Area Zone 22 not conductive dust and in not Ex Area After removal the lid the mounting holes are accessible The control is to be installed in a vibration free location Add on housing polyester The polyester add on housing can be installed indoors and outdoors under hard conditions The mechanical resistance is high Polyester is absolutely corrosion proof and high resis...

Page 9: ...ll as the relevant installation regulations Connect and carry the ground wire 4 2 Safety notes for the installation of the add on housing IMPORTANT NOTICE The unit must be installed such that the degree of protection IP 65 to EN 60529 is guaranteed state of delivery Therefore it is important to fix all screws of the lid to mount the cable entries competently to close unnecessary cable entries with...

Page 10: ...il info hainke de 27795 Hude 27798 Hude web www hainke de Operating Instructions electronic solenoid valve control type IFC 30 operating instructions Ifc30 ba_eng Version 02 2015 Date 26 02 2015 Page 9 cable entries from below mounting dimensions Illustration 4 1 Add on housing polycarbonate ...

Page 11: ... uniform distribution of the solenoid valves to the 3 output groups For example There are to connect 8 solenoid vales per output group if you have 24 solenoid vales complete Valve 1 8 to contact 1 8 Valve 9 16 to contact 11 18 Valve 17 24 to contact 21 28 The plus poles of the solenoid valves must be bound together and connected to contacts Connect the ground wire to PE on contact strip 1 It is al...

Page 12: ... Imbäke 7 email info hainke de 27795 Hude 27798 Hude web www hainke de Operating Instructions electronic solenoid valve control type IFC 30 operating instructions Ifc30 ba_eng Version 02 2015 Date 26 02 2015 Page 11 solenoid valve control IFC 30 Drawing 5 1 Electrical Connection ...

Page 13: ... the type plate which supply voltage is suitable for the unit on hand 110 120VAC and 220 240VAC or 24VDC Set the mains voltage switch 4 to the correct setting for the available supply voltage 110 120V or 220 240VAC Ensure that the correct fuse is inserted Refer to the technical data Pre select the outputs per group to be controlled by setting multi position switch 7 as desired Set the potentiomete...

Page 14: ...rational message green 20 only if controller is ACTIVE signal P yellow pessure switch input 21 dependents on switch status of connected trigger signal R yellow remote control 22 dependents on switch status of connected trigger output group 1 yellow 23 Start with remote control The dedusting process commences as soon as 1 signal is detected at input R The connected solenoid vales will be controlled...

Page 15: ...box 12 48 An der Imbäke 7 email info hainke de 27795 Hude 27798 Hude web www hainke de Operating Instructions electronic solenoid valve control type IFC 30 operating instructions Ifc30 ba_eng Version 02 2015 Date 26 02 2015 Page 14 Drawing 6 1 Front panel overview ...

Page 16: ...ontrol function is activated by setting DIP switch 1 19 to ON and de activated when that switch is set to OFF The DIP switch position may be changed whilst the controller is in operation If the remote control function is activated the dedusting process commences as soon as 1 signal is detected at input R LED 22 lights up If the remote control function is not active then dedusting commences as soon...

Page 17: ... Operating Pressure Test The nominal operating pressure in the pressure storage column can be monitored by connecting a pressure sensitive switch to input P contact strip 3 The following switch types may be connected to input P 1 Potential free contact normal pressure switch 2 Switch with electronic output PNP 3 Direct current between 12 and 30VDC against 0V The input is reverse polarity proof The...

Page 18: ...r the controller has been switched off via input R with reduced delay period The number of cleaning cycles can be set to between 0 and 5 via the selector switch If this switch is set to 0 there will be no post cleaning If the controller is switched OFF it will come to a standstill immediately following the end of any dedusting impulse operating mode STANDBY If the selector switch is set to values ...

Page 19: ...es off again From this results that the wire break fault was causes from the solenoid valve 5 8 1 Causes of fault and elimination Messages Indication Causes of Fault Elemination wire break LED red This indicator will go off when the next non faulty impulse is received No output load during the control impulse or short circuited valve output Check the adjusting of the multi position switch 7 The nu...

Page 20: ...eral Manager Herewith we declare that the electronic solenoid valve control IFC 30 in add on housing polycarbonate IP65 comply with following relevant regulations EC directive 2004 108 EG on electromagnetic compatibility EC low voltage directive 2006 95 EG EC directive 94 9 EG Equipment and protective systems intended for use in potentially explosive atmospheres Applied standards EN 61000 6 1 EN 6...

Reviews: