HL8002-MD Series Network Thermostat User Manual 

HL8002-MD Series Network thermostats are available for individual room temperature control 

in reside ntial, industrial an d busin ess premis es. Suita ble for 2-pip e F an Coil configur ation.

 

Network control is available (MODBUS). 

HL8002-MD adopts digital control techn ology with large LCD display, It  shows the follo wing 

items: working states (cool, heat or ventilation), the speed of fan coil, room temperature, set-point. 
There are following keys on the panel: On/Off “ ”, Exchange mode (cool, heat or ventilation) “ ”, 
timer “

¥

”, Select fan speed (high, medium, low or auto) “ ”, set-point temperature “

S

” and “

T

”. 

 

 

 

 

 

 

 

 

 

 

 

BASIC FEATURES                                                        STATUS DISPLAY 

 Room temperature setting 

 Manual or Auto 3-speed changeover 

 Defrost (low temperature protection) 

 Auto Restart (Option) 

 Clock, Sleep and Timer (Option) 

 IR remote control (Option) 

 Blue Backlight (Option) 

 RS485 Interface (MODBUS) 

 Working Status: Cool   ,  Heat   ,  Ventilation     

 Fan Speeds: Low 

 

, Medium    , High   and  

Auto   

 Room temperature display 

 Temperature setting display 

 Clock week display 

SPECIFICATIONS 

 Sensing element:     NT C 

 Accuracy :                      ± 1

 

 Set-point range:        5  to 35

 

 Display range:          0

50

 

 Operation environment: 0

45

 

 Operating Humidity:    5

90%RH (non-condensing) 

 Power supply:            AC 85

260V, 50/60Hz 

 Switch current rating: Resistive: 2A,    Inductive: 1A 

 Rated Power: 

<

 2 W 

 Wirings: Screw-in terminals, each terminal capable of 

accepting 2 x 1.5 mm

2

 or 1 x 2.5 mm

2

 wires 

 Housing: ABS + PC Flame Retardant 

 Dimensions: 86 × 86 × 13 mm ( W × H × D ) 

 Hole pitch: 60 mm ( Standard ) 

 Protection Class: IP30 

 Display: LCD 

OPERATION 

"

 On/Off: Press “ ” to turn on, press “ ” again to turn off thermostat and its output. 

"

 Setting temperature: Press “

T

” to reduce set-point, press “

S

” to raise set-point, and 1

 cha nged once. 

"

 Mode Selection: Press “ ” to change system working in cooling “ ”, heating “ ” or ventilation “ ” mode, the related 

icon will flash, and it will be confirmed automatically after 5 seconds. The ventilation function is invalid for HL8002Y-MD.

 

"

 F an Spe ed Selecti on (H L8002DA-MD/DB-MD): Press “ ” to chan ge f an sp eed  among “  (Hi)”,  “  (Med)”,  “  

(Low)” or “  (Auto)”. 

Under auto fan speed “ ”, the fan-speed will be changed automatically. Auto LOW-speed When the difference between 

room-temperature and set-point exceed 1

, Auto MED-speed When exceed 2

, Auto HI-speed When exceed 3

"

 Control Da mper (HL8 002Y-MD):  The damper  will be  open  when (1) room temperature is hig her than set-point  in  

cooling; (2) room temperature is lower than set-point in heating, Otherwise the damper will be closed. 

"

 Control Motorize d Valve  under 2-p ipe configurati on  (HL8002DA-MD/DB-MD): If the differenc e bet ween ro om 

temperature and set-point exceed 1

, FCU valve will be open; if room temper ature and set-point are equal, HL 8002DA-MD 

will close the FCU valve with the fan still running, HL8002DB-MD will close the FCU valve and Fan both. 

MODEL DENOMINATIONS

 

HL8002    

  

MD 

T: 

Clock, Sleep and timing on/off. Blank is invalid. 

R:

 IR remote function. Blank is invalid. 

(Remote controller should be ordered additionally)

L:

 Backlight available. Blank is invalid. 

Y:

        Control damper to open or close.

 

DA:

  Co ntrol Motorized Va lve for 2- wire N.C. F CU va lve and 3-sp eed fan; W hen t he temperatur e reaches t he 

set-point, it will close the Motorized Valve with the fan still running. 

DB:

  Co ntrol Motorized Va lve for 2- wire N.C. F CU va lve and 3-sp eed fan; W hen t he temperatur e reaches t he 

set-point, it will close both of the Motorized Valve and Fan. 

E:

 Auto Restart. Blank is invalid. 