Note:
1. Wire all circuits as Class 1, Electric Light or Power Circuits, including the Sensor input.
2. The length of the outside sensor cannot be longer than 45.72 ft. (15m). The sensor needs to be housed in a suitable plastic enclosure and the sensor leads voltage have to be rated
not less than the maximum rated line voltage of the device.
3. Only one sensor style: If only inside sensor’s fault, LCD shows “E0”; If only outside sensor’s fault, LCD shows “E1”.
Both inside and outside sensor: inside sensor fault, LCD shows ”E0”, outside sensor fault, LCD shows “E2”.
If any above fault happened, alarm will flash, and the thermostat will turn off the output
.
INSTALLATION
The device should be installed in place at least 32.81 ft. (10 meters) from the electrical service panel.
Note: Connect all wires as per the wiring
diagrams and keep it away from water, mud
and other materials.
1. Fix the mounting plate
with the screws.
2. Wire according to the
wiring program.
3. Push the button to install the
product into the mounting plate.
4. Lock the screw.