Notes:
When wiring, keep the distance between communication wire and power cable more than 10mm.
No.
Mark
Color
Meaning
1
A
White or green
12V
2
B
Red
on earth
3
C
yellow
communication
Note: Wire between indoor PCB and wired controller and the communication wire between indoor
and outdoor should be shieled wire, and the wire should be earthed at single point. Otherwise the
interference will affect the unit normal operation. Then confirm the terminals connected well and
not touch the shielded wire.
3.3 Install wired controller
Drill 2 holes in the wall according to the position of the two screws on the back of wired controller,
then fix the back cover of wired controller, install the front cover finally.
Note: Better install the wired controller on the flat wall. Don’t fasten too much or wired controller
will be damaged.
3.4 Install the top cover of wired controller, take care not to press the wires.
Note: Do not touch PCB with hand.
4. Cautions
Avoid switching on or off the unit frequently.
When you set one indoor at cooling mode (DRY) or heating mode, if the other indoors are in
different modes, this indoor will be at standby state.
Press TEMP. button to increase or reduce the set temperature, then the unit maybe stop, which is
not failure.
In cooling(or heating) mode, even indoor temp. is lower than (or higher than) the set temp., the unit
still is running in cooling (or heating) mode, which is not abnormal.
In DRY mode, fan speed will change automatically due to indoor temperature, which can not be
controlled by the fan speed button.
When wired controller is electrified for the 1
st
time, LCD will display all information for 2 seconds,
then LED and clock area will flash [88]
→
[8]
→
[88] for about 30 seconds. At this time, all buttons
are invalid.
If indoor requests fixed fan speed, you can not adjust the fan speed, and wired controller will
display FIX. If this model is equipped with AUTO RESTART function, when re-electrified, the unit
will display the original state before power is off.
Enter the mode of failure check
After entering the failure check mode, “18” in temp. area will display the unit number. “0” is the
actual connected indoor number (decimal), meanwhile, “88” in temp. area will display the latest
failure code (hex), and fan speed area will display “1”; press +/- button to check the former failure
code, and fan speed area will display “2”.
Every time you press “CHECK” button, unit number will increase 1 untill it is 15; press again, it is
“0”, then recycle. That is cycling as 0
~
15
~
0.
If within 5 seconds, no pressing “CHECK” button, it will quit the failure check mode automatically.
Cancel failure history: in normal state, press “CHECK” for 5 seconds continuously, you will cancel
the failure history.
Jumper description:
ON
Without auto restart
Auto restart
JP4
OFF
With auto restart
ON
Display indoor temp.
Display indoor temp.
or not
JP2
OFF
Not display indoor temp.
ON
In cooling mode, not limit to set temperature
26
℃
lock
JP3
OFF
In cooling mode, limit the set temp. below 26
℃
ON
With time-shorting
Time-shorting
JP1
OFF
Without