Notes:   
When wiring, keep the distance between communication wire and power cable more than 10mm. 
No. 

Mark 

Color 

Meaning 

White or green 

12V 

Red 

on earth 

yellow 

communication 

 
Note: Wire between indoor PCB and wired controller and the communication wire between indoor 
and outdoor should be shieled wire, and the wire should be earthed at single point. Otherwise the 
interference will affect the unit normal operation. Then confirm the terminals connected well and 
not touch the shielded wire. 
3.3 Install wired controller 

Drill 2 holes in the wall according to the position of the two screws on the back of wired controller, 
then fix the back cover of wired controller, install the front cover finally. 

Note: Better install the wired controller on the flat wall. Don’t fasten too much or wired controller 
will be damaged. 
3.4 Install the top cover of wired controller, take care not to press the wires. 
Note: Do not touch PCB with hand. 
4. Cautions 
Avoid switching on or off the unit frequently. 
When you set one indoor at cooling mode (DRY) or heating mode, if the other indoors are in 
different modes, this indoor will be at standby state.   
Press TEMP. button to increase or reduce the set temperature, then the unit maybe stop, which is 
not failure.   

In cooling(or heating) mode, even indoor temp. is lower than (or higher than) the set temp., the unit 
still is running in cooling (or heating) mode, which is not abnormal.   

In DRY mode, fan speed will change automatically due to indoor temperature, which can not be 
controlled by the fan speed button. 
When wired controller is electrified for the 1

st

 time, LCD will display all information for 2 seconds, 

then LED and clock area will flash [88]

[8] 

[88] for about 30 seconds. At this time, all buttons 

are invalid. 
If indoor requests fixed fan speed, you can not adjust the fan speed, and wired controller will 
display FIX. If this model is equipped with AUTO RESTART function, when re-electrified, the unit 
will display the original state before power is off.   
Enter the mode of failure check 
After entering the failure check mode, “18” in temp. area will display the unit number. “0” is the 
actual connected indoor number (decimal), meanwhile, “88” in temp. area will display the latest 
failure code (hex), and fan speed area will display “1”; press +/- button to check the former failure 
code, and fan speed area will display “2”. 
Every time you press “CHECK” button, unit number will increase 1 untill it is 15; press again, it is 
“0”, then recycle. That is cycling as 0

15

0. 

If within 5 seconds, no pressing “CHECK” button, it will quit the failure check mode automatically.   
Cancel failure history: in normal state, press “CHECK” for 5 seconds continuously, you will cancel 
the failure history. 
 

Jumper description: 

ON 

Without auto restart 

Auto restart 

JP4 

OFF 

With auto restart 

ON 

Display indoor temp. 

Display indoor temp. 

or not 

JP2 

OFF 

Not display indoor temp. 

ON 

In cooling mode, not limit to set temperature 

26

 lock 

JP3 

OFF 

In cooling mode, limit the set temp. below 26

 

ON 

With time-shorting 

Time-shorting 

JP1 

OFF 

Without 

 