Seivice diagnosis
Domestic air conditioner
11.4.6 Over-current of the compressor
Electrify the machine again and turn it on
with the remote controller, If malfunctions
are reported before or upon the compressor
being started up,
IPM Module is damaged and
needs replacing.
Repair the power supply
the system may have been over or under charged
with gas, which can be judged through the
pressure of the measuring system.
YES
NO
Yes
NO
The compressor is started normally, but
malfunctions are reported after it has
run for some time. Check the power
supply is too low or too high
NO
Method of
malfunction detection
Malfunction detection
conditions
Troubleshooting
he current of the compressor is too high
when the IPM Module is damaged or the compressor is damaged. power supply
voltage is too low or too high
Supposed causes
LED1 flash 3 or 24 or 25 times
Outdoor diplay
Ŷ
Faulty IPM Module
Ŷ
Faulty compressor
Ŷ
Faulty power supply
* Caution
Be sure to turn off power switch before connect or disconnect connector, or parts
damage may be occurred..
.
37
Summary of Contents for N-Series
Page 47: ...Circuit diagrams Domestic air conditioner 12 Circuit diagrams 45 ...
Page 48: ...Circuit diagrams Domestic air conditioner 46 ...
Page 51: ...Removal of procedure 1 Removal of Air Filter 1 Domestic Air Condition ...
Page 54: ...Removal of procedure three two HOOKS 4 Domestic Air Condition ...
Page 56: ...Removal of procedure 4 Removal of Drain pan 6 Domestic Air Condition ...
Page 57: ...Removal of procedure 5 Removal of vertical blades and swing motor 7 Domestic Air Condition ...
Page 58: ...Removal of procedure 6 Removal of Electrical Box 8 Domestic Air Condition ...
Page 59: ...Removal of procedure 7 Removal of Heat Exchanger 9 Domestic Air Condition ...
Page 60: ...Removal of procedure 10 Domestic Air Condition ...
Page 61: ...Removal of procedure 8 Removal of Fan Rotor and Motor 11 Domestic Air Condition ...
Page 62: ...Removal of procedure 12 Domestic Air Condition ...