H. Set EEV open angle by hand
When being switched off, short connect CN27 to open the valve fully compulsorily for 2 minutes;
When being switched off, short connect CN29 to close the valve fully compulsorily for 2 minutes.
I. Anti-freezed protection
In cooling mode, execute the anti-freezed protection due to the measured indoor coil temp. to avoid
the indoor heat exchanger causeing frost or ice.
J. Other functions
a. Swing motor control
Indoor will control swing motor ON/OFF due to the swing signal from wired controller.
b. Auxiliary electric heater control
In heating mode, if the below conditions can be met, the electric heater will work:
(1) Indoor fan motor and compressor are running;
(2) Air inlet temp. is no more than 22
¡
;
(3) Room temp. is lower over 2
¡
than the set temp.;
(4) Compressor has run for 5 seconds;
Either below condition is met, the electric heater will stop:
(1) Indoor fan motor or compressor not runs;
(2) Indoor air inlet temp. is over 23
¡
;
(3) Indoor air inlet temp. is higher over -1
¡
than the set temp.;
(4) Unit stops or quit the heating mode.
c. Filter cleaning
Check and memorize the running time of indoor fan motor, once arriving the requested time (set
by SW07-6), indoor will send filter cleaning signal to wired controller; when indoor recieves the filter
reset signal from wired controller, if the time exceeds the requested time, the filter will reset.
d. Compulsory defrosting: after indoor receives the compulsory defrosting signal from wired controller,
it will send compulsory defrosting signal to outdoor contineously for 10 times. In the sending period,
indoor will execute the normal defrost.
e. Trial operation
Set the mode as cooling (heating), press ON/OFF for 5 seconds to enter compulsory cooling (heating).
In compulsory cooling, display "LL" and COOL will flash;
In compulsory heating, display "HH" and HEAT will flash, fan speed is AUTO.
At this time, only ON/OFF, TEMP +/- are valid.
3.2 Wired controller
When wired controller is electrified for the first time,
the controller will display all info for 2 seconds, then
LED and CLOCK area will change:"8888"
¡œ
"888"
¡œ
"88"
¡œ
"8"
and flash for about 30 seconds, all
buttons are invalid.
C
HEALTH
F
MODE
FAN
SWING
TEMP
CLOCK
TIMER
SET
RECOVERY
CHECK
FILTER
RESET
MODE
FAN
AUTO
AUTO
FAN ONLY
COOL
DRY
HEAT
TES
HIGH
MED
LOW
FIX
CENTRAL
OPERATION
STANDBY
PRE-HEAT
DEFROST
FILTER
HEALTH
CHECK
SWING
UNIT NO.
DEMAND
MANUAL
CEN.ADD.
SYS.ADD.
ROOM TEMP.
SET TEMP.
TIMER CLOCK UP DOWN VENTILATION
ON
OFF
DAILY
AUTO
RECOVERY
NORMAL
ON/OFF
Summary of Contents for MRV II AV48NMVERA
Page 6: ...G R U P A d o o 06 2 Wiring work ...
Page 40: ...G R U P A d o o 40 ...