Service diagnosis
31
Domestic air conditioner
10.3.3 Indoor DC fan motor malfunction
Indoor Display
E14
Method of
The rotation speed detected by the Hall IC during fan motor operation is used to determine
Malfunction
abnormal fan motor operation
Detection
Malfunction
when the detected rotation feedback signal don’t received in 2 minutes
Decision
Conditions
Supposed
Operation halt due to breaking of wire inside the fan motor.
Causes
Operation halt due to breaking of the fan motor lead wires
Detection error due to faulty indoor unit PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
Check whether
terminals on indoor
pcb is well
Pull out the term inals on
the indoor mainboard and
reinsert them.
Turn off power switch,and pull out the fan motor.
Measure the resistances between balck line (0V)and white
line(15V) ,balck line (0V)and red line(310V) of indoor fan motor .
The
resistances range is
between 30K
Ω
with
2M
Ω
The
indoor fan
motor is damaged
and need replace
NO
YES
NO
YES
the ind oor pcb is dam aged
and need replace
Summary of Contents for JS035-D2
Page 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 EEV EEV ...
Page 14: ...Printed circuit board connector wiring diagram 12 Domestic air conditioner PCB 1 ...
Page 46: ......
Page 51: ...three 6 Removal Procedure 4 Domestic Air Conditioner Remove the casing 1 2 3 ...
Page 55: ...Removal Procedure 8 Domestic Air Conditioner motor cover motor cover ...
Page 56: ...Removal Procedure 9 Domestic Air Conditioner ...