Indoor unit

Make a hole of 70 mm (2 3/4) in diameter, slightly descending to outside the wall.

ƽ

Install piping hole cover and seal it off with putty after installation

ƽ

When the mounting plate is first fixed

1. Carry out, based on the wall studs or lintels, a 

to be fixed against the wall, then temporarily fasten the plate with one steel nail.

2. Make sure once more the proper level of the plate, by hanging a thread with a 

weight from the central top of the plate, then fasten the plate.

3. Find the wall hole location A using a measuring tape

Fitting of the Mounting Plate and Positioning of the wall Hole

Lid for right
piping

Lid for under piping pipe

Fix with adhesive tape

Lid for left piping

Indoor/outdoor electric cable and drain hose must be bound with refrigerant

ƽ

[ Other piping direction ]

Cut away, with a nipper, the lid for piping according to the piping direction and

ƽ

then bend the pipe according to the position of wall hole. When bending, be

careful not to crush pipes.

Connect beforehand the indoor/outdoor electric cable,

ƽ

and then pull out the

connected to the heat insulation of connecting part specially.

proper leveling for the plate

Making a Hole on the Wall and Fitting the Piping Hole Cover

Drawing of pipe

Installation of the Indoor Unit

[ Rear piping  ]

Draw pipes and the drain hose, then fasten them with the adhesive tape

ƽ

[ Left

·

Left-rear piping ]

In case of left side piping, cut away, with a nipper, the lid for left piping.

ƽ

In case of left-rear piping, bend the pipes according to the piping direction to

ƽ

the mark of hole for left-rear piping which is marked on heat insulation materials.

1. Insert the drain hose into the carity of heat insulation materials of indoor unit.
2. Insert the indoor/outdoor electric cable from backside of  indoor unit, and pull it

out on the front side, then connect them.

3. Coat the flaring seal face with refrigerant oil and connect pipes.

Fixing the indoor unit body

ƽ

In order to fix the body onto the mounting plate,hold up

ƽ

the body at a slant from the underside and then put it down
perpendicularly.

Connecting the indoor/outdoor Electric Cable

Removing the wiring cover

Remove terminal cover at right bottom corner of indoor unit, then take

ƽ

 off wiring cover by removing its screws.

1. Insert from outside the room cable into left side of the wall

hole, in which the pipe has already existed.

2. Pull out the cable on the front side, and connect the cable

making a loop.

Note

When connecting the cable, confirm the terminal number of indoor and
outdoor units carefully. If wiring is not correct, improper operation may

ƽ
ƽ
ƽ

mounting plate

When connecting the cable after installing the indoor unit

When connecting the cable before installing the indoor unit

When you unload the indoor unit, please use 

bottom of the body outward slightly
and lift the unit until it leaves the
mounting plate. 

mounting plate

Unloading of indoor unit body

ƽ

your hand to raise the body, then lift the 

Remote controller (1)

AAA dry battery (2)

Mounting plate (1)

Drain hose (1)

Ø4X25 Screw (4)

Plastic cap (4)

Drain-elbow (1)

Cushion (4)

Pipe supporting plate (1)

Accessory parts

NOTE

˖

The thickness of the pipe must be 0.8mm(1/16”) at least.

Selection of pipe

2

Insert the cord from the back side of the unit, then pull it out on the front side.

Fasten the unit wire harness to the conduit holder using the lock nut.

Position the conduit holder to its original state using screw.

Conduit holder

Cut the 6 slit sear

Cover the connection part with heat insulation materials, cover with adhesive tape. 

piping with protecting tape.

Hang the unit body securely onto the upper notches of the

mounting plate. Move the body from side to side to verify 
its secure fixing.

Indoor side

Outdoor side

Ø70mm

Wall hole

Thickness of wall

Heat insulation
material

Drain hose

Piping

Pipe supporting
plate

Indoor/outdoor electric cable

Liquid pipe (Ø)

6.35mm(1/4”)

Gas pipe (Ø)

9.52mm(3/8”)

A=145mm

35mm

B=

70mm

Ø

For 09K 12K

For 18K 

6.35mm(1/4”)

12.7mm(1/2”)

A=150mm

B= 70mm

35mm

Type

For 24K

9.52mm(3/8”)

15.88mm(5/8”)

A=145mm

B=

70mm

Ø

30mm

occur and cause damage to the units.

(2 3/4)

(5 5/7)

(1 3/8)

(2 3/4)

(1 1/6)

(5 5/7)

(2 3/4)

(5 7/8)

(1 3/8)

(2 3/4)

Pitch downward for drainage