background image

If the drain-elbow is used,

ƽ

please attach it as figure. (Note:
Only for heat pump unit.)

Detach the service port’s cap of

1.

3-way valve, the valve rod’s cap for 2-way valve

and 3-way’s, connect the service port into the projection of charge hose (Iow)

for gaugemanifold. Then connect the projection of charge hose (center) for gau-

gemanifold into vacuum pump.

Open the handle at Iow in

2.

gaugemanifold, operate vacuum pump. If the scale-

moves of gause (Iow) reach vacuum condition in a moment, check 1. again.

Vacuumize for over 15min.And check the level gauge which should read -0.1MPa

3.

(76 cm Hg) at Iow pressure side. After the completion of vacuumizing, close the

handle ‘Lo’ in gaugemanifold and stop the operation of the vacuum pump. Check

condition of the scale and hold it for 1-2min. If the scale-moves back in spite of

tightening, make flaring work again, the return to the beginning of 3 .

Attaching Drain-Elbow

Purging Method:To use vacuum pump

Open

Open the valve rod for the 2-way valve to an angle  of

4.

anticlockwise 90 degrees.

After 6 seconds, close the 2-way valve and make the inspection of gas leakage.

No gas leakage?

5.

Detach the charge hose

6.

from the service port, open 2-way valve and 3-way. Turn

the valve rod anticlockwise until hitting lightly.

In case of gas leakage, tighten parts of pipe connection. If

leakage stops, then proceed 6. steps

If it does not stop gas leakage, discharge whole refrigerants from the service

port. After flaring  work again and vacuumize, fill up prescribed

refrigerant from the gas cylinder.

Anti countercurrent joint

Gaugemanifold(for R410A)

2-way valve Liquid Side

3-way valve Gas Side

Vacuum pump(for R410A)

Tube(for R410A)

Close

2-way valve

3-way valve

Open 90

O

2-way valve

3-way valve

2-way valve 3-way valve

2-way valve

3-way valve

Valve rod cap

Valve rod cap

Service port cap

To prevent the gas leakage, turn the service port’s cap, the valve rod’s cap for 2-wa

valve and 3-way’s a little more than the point where the torque increases suddenly

After attaching the each caps, check the gas leakage around the caps.

7.

8.

Step 1.

Step 2.

Step 3.

Step 7.

Step 6.

Step 4.

The power source must be exclusively used for air

ƽ

conditioner. (Over I0A)

In the case of installing an air conditioner in a moist place,

ƽ

please install an ea-

For installation in other places, use a circuit breaker as far

ƽ

as possible.

Pipe cutting is carried out with a pipe cutter and burs must

ƽ

be removed.

After inserting the flare nut, flaring  work is carried out.

ƽ

If the refrigerant of the air conditioner leaks, it is necessary to discharge all the

ƽ

refrigerant. Vacuumize first, then charge the liquid refrigerant into air conditio-
ner according to the amount marked on the name plate.

Please do not let other cooling medium, except specified one (R410A), or air

ƽ

enter into the cooling circulation system. Otherwise, there will be abnormal
high pressure in the system to make it crack and lead to personal injuries.

Power Source Installation

Cutting and Flaring Work of Piping

Flare tooling die

1.Cut pipe

2.Remove burs

3.Insert the flare nut

CAUTION

Flare tool for R410A

Conventional flare tool

Clutch-type

clutch-type(Rigid-type) Wing-nut type (Imperial-type)

A

0~0.5mm

1.0~1.5mm

1.5~2.0mm

rth leakage breaker.

4.Flare pipe

Lean

Damage of flare

Partial

Too outside

Correct

Incorrect

On Drainage

It becomes

high midway.

The gap with the

ground is too small.

There is the bad
smell from a ditch

It waves.

The end is imm-
ersed in water.

Please install the drain hose so as to be downward slope without fail.
Please don’t do the drainage as shown below.

ƽ
ƽ

Please pour water in the drain pan of the indoor unit, and

ƽ

is carried out surely to outdoor.

In case that the attached drain hose is in a room, please

ƽ

apply heat insulation to

Less than

5cm

confirm that drainage

it without fail.

4

Check Items for Test Run

Gas leak from pipe connecting?

Heat insulation of pipe connecting?

Are the connecting wirings of indoor and outdoor firmly

Is the connecting wiring of indoor and outdoor firmly fixed?

Is drainage securely carried out?

Is the earth line securely connected?

Is the indoor unit securely fixed?
Is power source voltage abided by the code?

Is there any noise?

Is the lamp normally lighting?
Are cooling and heating (when in heat pump) performed normally?

Is the operation of room temperature regulator normal?

Please kindly explain to our customers how to operate
through the instruction manual.

Check for Installation and Test Run

Ƶ

inserted to the terminal block?

Ƶ

1

1+2=

kg

R410A

2

kg

2=

1=

B

C

D

F

E

kg

A

This product contains fluorinated greenhouse gases covered by 
the Kyoto Protocol. Do not vent into the atmosphere.
Refrigerant type:R410A
GWP* value:1975
GWP=global warming potential
Please fill in with indelible ink,
• 1      the factory refrigerant charge of the product
• 2      the additional refrigerant amount charged in the field and
• 1+2  the total refrigerant charge
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product
charging port (e.g. onto the inside of the stop value cover).
A  contains fluorinated greenhouse gases covered by the Kyoto 
Protocol
B  factory refrigerant charge of the product: see unit name plate
C   additional refrigerant amount charged in the field
D   total refrigerant charge
E   outdoor unit
F   refrigerant cylinder and manifold for charging 

Contains fluorinated greenhouse gases
covered by the Kyoto Protocol

Refrigerant charge label

Ƶ

Put check mark

in boxes

Crack

 

Summary of Contents for HSU- 09HA103/R2

Page 1: ...age without fail The power source is the same as the corresponding name plate Install an exclusive branch circuit of the power A receptacle shall be set up in a distance where the power cable can be r...

Page 2: ...e front side then connect them 3 Coat the aring seal face with refrigerant oil and connect pipes Cover the connection part with heat insulation materials closely and make sure xing with adhesive tape...

Page 3: ...e function of the unit will be affected If the pipe has to be lengthened the refrigerant should be charged according to 20 g m But the charge of refrigerant must be conducted by profes sional air cond...

Page 4: ...conditio ner according to the amount marked on the name plate Please do not let other cooling medium except speci ed one R410A or air enter into the cooling circulation system Otherwise there will be...

Page 5: ...de la unidad y que no ampli que el ruido y las vibraciones Seleccione un lugar en el que los residuos y el viento generado por la unidad no cause una molestia a los vecinos Coloque la unidad en un lug...

Page 6: ...gerante utilizando cinta protectora Entubaci n en otra direcci n Corte con una cuchilla la cubierta de entubaci n de acuerdo con la direcci n de entubaci n y doble los tubos de acuerdo con la posici n...

Page 7: ...idad interior Unidad exterior Unidad interior Elevaci n m x Am x 10m En caso de que la elevaci n A sea superior a 5m el filtro de aceite debe instalarse cada 5 7 m Longitud m x Bm x 15m En caso de que...

Page 8: ...e contiene el producto de f brica 2 La cantidad de refrigerante adicional cargada durante la instalaci n y 1 2 La carga total de refrigerante en la etiqueta de refrigerante suministrada con el product...

Page 9: ...o dell unit dove le vibrazioni ed il rumore non siano aumentati Luogo dove l aria di scarico ed il rumore non provocano disturbo ai vicini di casa Luogo dove sia disponibile una distanza contrassegnat...

Page 10: ...la direzione della stessa e piegarla in base alla posizione del foro sulla parete Quando si piega prestare attenzione e non spaccare i tubi Connettere prima il cavo elettrico interno esterno quindi es...

Page 11: ...te eseguire lo s ato dell aria dalle tubature del refrigerante e dall unit interna usando una pompa a vuoto poi caricare il refrigerante A B A B A B AVVERTENZA Unit interna Unit da esterno Unit da est...

Page 12: ...ante forni ta col prodotto L etichetta compilata deve essere attaccata accanto alla porta di caricamento del prodotto es all interno del coperchio con il valore di arresto A Questo prodotto contiene g...

Page 13: ...ez un emplacement capable de supporter l unit o les vibrations et le bruit n augmentent pas S lectionnez un emplacement o le vent et le bruit ne risquent pas de g ner les voisins Choisir un endroit da...

Page 14: ...eures ext rieures et le tuyau de vidange doivent tre x s au tuyau de r frig rant avec un ruban protecteur Tuyauterie dans une autre direction A l aide d une pince d coupez le couvercle pour la tuyaute...

Page 15: ...suite le r frig rant suppl mentaire A B A B A B AVERTISSEMENT Unit int rieure Unit ext rieure Unit ext rieure Pi ge dl huile Unit int rieure Unit ext rieure Unit int rieure Hauteur max Amax 10m Si la...

Page 16: ...an te Merci de remplir l encre ind l bile 1 la charge de r frig rant standard de l appareil 2 la quantit suppl mentaire de r frig rant charg e sur place et 1 2 charge totale de r frig rant sur l tique...

Reviews: