background image

1.Cut pipe

3.Insert the flare nut

4.Flare pipe

It becomes high midway.

The end is immersed
in water.

It waves.

The gap with the ground
is too small

Less than 5cm

There is the bad smell
from a ditch

2.Remove burs

0~0.5mm

1.0~1.5mm

1.5~2.0mm

Flare tool for R410A

Clutch-type

Conventional flare tool

clutch-type(Rigid-type) Wing-nut type (Imperial-type)

1.Power Source Installation

2.Cutting and Flaring Work of Piping

3.On Drainage

Check for Installation and Test Run

Check Items for Test Run

The power source must be exclusively used for air conditioner. (Over I0A)
In the case of installing an air conditioner in a moist place, please install an
earth leakage breaker.
For installation in other places, use a circuit breaker as far as possible.

Pipe cutting is carried out with a pipe cutter and burs must be removed.
After inserting the flare nut, flaring work is carried out.

Please install the drain hose so as to be downward slope without fail.
Please don't do the drainage as shown below.

Please pour water in the drain pan of the indoor unit, and confirm that drainage is
carried out surely to outdoor.
In case that the attached drain hose is in a room, please apply heat insulation
to it without fail.

Please kindly explain to our customers how to operate through the instruction manual.

Gas leak from pipe connecting?
Heat insulation of pipe connecting?
Are the connecting wirings of
indoor and outdoor firmly inserted
to the terminal block?
Is the connecting wiring of indoor
and outdoor firmly fixed?

Is drainage securely carried out?
Is the earth line securely
connected?
Is the indoor unit securely fixed?
Is power source voltage abided
by the code?
Is there any noise?

Put check mark       in boxes

Is the lamp normally lighting?
Are cooling and heating (when
in heat pump) performed normally?
Is the operation of room temperature
regulator normal?

Flare tooling die

Correct

Incorrect

Lean Damage of flare Crack

Partial

Too outside

8

A

A

Summary of Contents for HSU-07HVA103

Page 1: ...e 9 Nipper 12 Reamer 10 Gas leakage detector or soap and water solution 11 Measuring tape Explain sufficiently the operating means to the user according to this manual A G G F A C D E No Accessory par...

Page 2: ...ated Place possible to bear the unit where vibration and noise are not increased Place where discharged wind and noise do not cause a nuisance to the neighbors Place where a distance marked is availab...

Page 3: ...article When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make...

Page 4: ...the underside and then put it down perpendicularly Remove terminal cover at right bottom corner of indoor unit then take off wiring cover by removing its screws When connecting the cable after instal...

Page 5: ...e cable from the back side of the unit then pull it out on the front side Loosen the screws and insert the cable ends fully into terminal block then tighten the screws Pull the cable slightly to make...

Page 6: ...neer Before adding additional refrigerant perform air purging from the refrigerant pipes and indoor unit using a vacuum pump then charge additional refrigerant Use the same method on indoor unit Loose...

Page 7: ...steps Detach the charge hose from the service port open 2 way valve and 3 way Turn the valve rod anticlockwise until hitting lightly To prevent the gas leakage turn the service port s cap the valve ro...

Page 8: ...ried out Please install the drain hose so as to be downward slope without fail Please don t do the drainage as shown below Please pour water in the drain pan of the indoor unit and confirm that draina...