English
Installation, Use and Maintenance Manual - HACI-RP DX series
pag. 46
-
Screensaving:
1
There are five kinds of screen saving time. The time means that how long screen light continues lightening without operation. “Cancel”
means that the screen light will keep lightening. The default screen saving time is 15s.
-
Brightness:
2
The Brightness function is used for controlling the brightness of screen light and the default value is 80%.
-
Set outlet temperature display:
3
Choose “Yes”, outlet temp. will display in the main interface. Choose “No”, outlet temp. will not display in the main interface.
-
Temperature unit:
4
Celsius and Fahrenheit can be shifted freely.
Communication with central controller
- The wired controller will display ”Central” icon to show central control mode after receiving central control signal from indoor unit. All keys
1
except “ON/OFF” of wired controller become invalid. Central icon will disappear if no central signal from indoor unit.
- When receiving locking signal from indoor unit, “Lock” icon will statically display in the wired controller and all keys become invalid.
2
4.1.6 Wired Controller Wiring Instruction
Di seguito gli schemi di connessione del controllore cablato:
Communication wiring:
Communication wiring length (m. / ft.)
Dimensions of wiring
< 100 m. / 328 ft.
0.3 mm
2
x3 - core shielded wire (22AWG, 3 wire)
≥
100 m. / 328 ft. and < 200 m. / 656 ft.
0.5 mm
2
x3 - core shielded wire (20AWG, 3 wire)
≥
200 m. / 656 ft. and < 300 m. / 984 ft.
0.75 mm
2
x3 - core shielded wire (18AWG, 3 wire)
* One side of the shielded sheet of communication wire must be earthed.
Controller Installation:
- Pass the communication cable through the hole of the concealed box.
1
- Pass the cable through the back cover of the wired controller at the place No.1
2
- Mounted the back cover on the concealed box by screws.
3
Wired Controller Wiring Instruction
- Plug the terminals of the communication cables on the corresponding connectors, and
1
slide the front cover of the wired controller from up to down, then fixed.
- White wire, connected to indoor A, Yellow wire, connected to indoor B, Red wire, con-
2
nected to indoor C.s
Summary of Contents for HACI-RP DX 100
Page 52: ...2020 06 ...