Occupancy Sensors (optional)*
A wireless door sensor (located on guest entry door) and motion sensor (ceiling or wall mount)
communicate to the Zoneline through a Setback Module. The three components work collectively to
determine whether the room is occupied or vacant. When the guest room door is opened and motion
is sensed, the MUAM will turn on and remain running (depending outdoor temperature and humidity).
When the door is opened again (the guest is exiting the room) and no motion is detected within five
minutes, the MUAM will turn off. If someone is in the room and motion is detected or the door is again
opened the MUAM will cycle back on.
CDC (Central Desk Control) (optional)*
The CDC input on Zoneline is an occupancy control option which is operated by the Property
Management. A field provided switch wired to the CDC connector can open/close the circuit to
stop operation of the Zoneline when closed, and when open the Zoneline is operational. The CDC
connector can be used with an occupancy detection system to, instead, control the operation of the
MUAM. Such a system is optional and is enabled through the Aux menu. It should be noted that if an
occupancy detection system is enabled with a digital Make Up Air (*DBM and *EBM) Model, Central
Desk Control cannot be used at the same time.
If the occupancy system is the suspect failure (confirm that Auxiliary Settings are turned on, see
Auxiliary Controls
section and
Auxiliary Set Button
section), the diagnosis can be verified by
unplugging the CDC connector. With the Zoneline turned off, the fans will be heard. If the fans cannot
be heard, enter Service Mode to turn the fan speed higher to verify operation.
*Occupancy Sensors and CDC are Optional accessories, only one may be used.
Door Sensor
Motion Sensor
Guest Door
Zoneline
Wireless Signal
Wireless Signal