HAIER CHILLER
Water inlet temp.
sensor failure
Last for 5 seconds, chiller downloads
and stops, the water pump will not stop
Press “reset” after troubleshooting,
stop water pump later, press ”ON”
to restart.
Discharging temp.
sensor failure
Last for 5 seconds, chiller downloads
and stops, the water pump will not stop
Press “reset” after troubleshooting,
stop water pump later, press ”ON”
to restart.
Fin temp. sensor
failure
Last for 5 seconds, chiller downloads
and stops, the water pump will not stop
Press “reset” after troubleshooting,
stop water pump later, press ”ON”
to restart.
Heat pump
model
Discharging pressure
sensor failure
Last for 5 seconds, chiller downloads
and stops, the water pump will not stop
Press “reset” after troubleshooting,
stop water pump later, press ”ON”
to restart.
Can not
short circuit
Suction pressure
sensor failure
Chiller stops immediately, alarm
discharging protection, then alarm
discharging failure.
Press “reset” after troubleshooting,
stop water pump later, press ”ON”
to restart.
。
Can not
short circuit
P CB 0 0 10 45 29 32 photo
41