TECHNICAL OVERVIEW
PAGE 16
ENGLISH
4 Way Valve
The 4 Way Valve is energized during heating mode operation.
The valve is energized with 230 volts via a connection plug on
the ECU. When energized, the valve directs the compressor
hot gas to the indoor coil.
During Cooling mode and Defrost mode operation, the valve
is de-energized. When de-energized, the valve will direct the
compressor hot gas to the outdoor coil.
Outdoor Fan Motor
The Outdoor Fan Motor is a variable speed motor. The motor
is energized via a connection plug on the ECU. The motor
is powered by line voltage from the ECU. The motor has a
PWM circuit that feeds back voltage to the ECU. The ECU will
control the speed of the motor by a DC voltage applied to the
yellow wire of the connection plug. The feedback PWM signal
from the fan motor is applied to the ECU via the blue wire on
the connection plug.
Outdoor
Fan Motor
Low
Pressure
Switch
Low Pressure Switch
The system has a Low Pressure Switch that will shut down
system operation if abnormally low refrigeration circuit
pressure is detected. This switch is connected to the ECU
via an electrical plug. During normal operation this switch
will be closed.
If the switch were to open during a call for cooling or heating
mode operation, the system will shut off the compressor
and display an error code. If the pressure rises to re-close
the switch, the compressor will re-start and continue on
with normal operation. Multiple cycles of opening and
closing the switch will cause the system to lock out and
display an Error Code 43.
Causes of low refrigerant pressure include leaks,
undercharging, restrictions, EEV failure and cold room air
temperatures/dirty indoor coils/restricted airflow at indoor
unit.
High Pressure Switch
The system has a High Pressure Switch that will shut down
system operation if abnormally high refrigeration circuit
pressure is detected. This switch is connected to the ECU via
an electrical plug. During normal operation this switch will be
closed.
If the switch were to open during a call for cooling or heating
mode operation, the system will shut off the compressor and
display an error code. If the pressure drops to re-close the
switch, the compressor will re-start and continue on with
normal operation. Multiple cycles of opening and closing the
switch will cause the system to lock out and display an Error
Code 42.
Causes of high refrigerant pressure include overcharging,
restrictions, EEV failure, and dirty outdoor coil.
High
Pressure
Switch
OUTDOOR UNIT TECHNICAL OVERVIEW
Outdoor Unit Components
4 Way Valve
Summary of Contents for AW07LC2VHA
Page 3: ...PAGE 3 ENGLISH INTRODUCTION SPECIFICATIONS Multi Zone Indoor...
Page 4: ...PAGE 4 ENGLISH INTRODUCTION SPECIFICATIONS Multi Zone Indoor...
Page 5: ...PAGE 5 ENGLISH INTRODUCTION SPECIFICATIONS Multi Zone Outdoor...
Page 73: ...REFERENCES PAGE 73 ENGLISH Component Ratings REFERENCES...
Page 76: ...REFERENCES PAGE 76 ENGLISH Wiring REFERENCES...
Page 77: ...REFERENCES PAGE 77 ENGLISH Wiring REFERENCES...
Page 78: ...REFERENCES PAGE 78 ENGLISH Wiring REFERENCES...
Page 79: ...REFERENCES PAGE 79 ENGLISH Wiring REFERENCES...
Page 80: ...REFERENCES PAGE 80 ENGLISH Wiring REFERENCES...
Page 81: ...REFERENCES PAGE 81 ENGLISH 2U Wiring REFERENCES...
Page 82: ...REFERENCES PAGE 82 ENGLISH CN20 Connector for room card Wiring REFERENCES...
Page 83: ...REFERENCES PAGE 83 ENGLISH SWI Wiring REFERENCES...
Page 84: ...REFERENCES PAGE 84 ENGLISH Wiring REFERENCES...
Page 86: ...REFERENCES PAGE 86 ENGLISH CIRCUIT DIAGRAMS REFERENCES...
Page 87: ...REFERENCES PAGE 87 ENGLISH CIRCUIT DIAGRAMS REFERENCES...
Page 88: ...REFERENCES PAGE 88 ENGLISH WIRING DIAGRAMS REFERENCES...
Page 89: ...REFERENCES PAGE 89 ENGLISH WIRING DIAGRAMS REFERENCES...
Page 90: ...REFERENCES PAGE 90 ENGLISH 2U Piping Installation Dimensions REFERENCES...
Page 92: ...REFERENCES PAGE 92 ENGLISH Refrigerant Diagram REFERENCES...
Page 93: ...REFERENCES PAGE 93 ENGLISH Refrigerant Diagram REFERENCES...
Page 94: ...REFERENCES PAGE 94 ENGLISH 3U Piping Installation Dimensions REFERENCES...
Page 95: ...REFERENCES PAGE 95 ENGLISH 4U Piping Installation Dimensions REFERENCES...
Page 110: ...REFERENCES PAGE 110 ENGLISH SENSORS Value of Thermistor Indoor Unit...
Page 111: ...REFERENCES PAGE 111 ENGLISH SENSORS...
Page 112: ...REFERENCES PAGE 112 ENGLISH SENSORS...
Page 113: ...REFERENCES PAGE 113 ENGLISH SENSORS...
Page 114: ...REFERENCES PAGE 114 ENGLISH SENSORS...
Page 115: ...REFERENCES PAGE 115 ENGLISH SENSORS...
Page 116: ...REFERENCES PAGE 116 ENGLISH SENSORS...
Page 117: ...REFERENCES PAGE 117 ENGLISH SENSORS...
Page 118: ...REFERENCES PAGE 118 ENGLISH SENSORS...
Page 119: ...REFERENCES PAGE 119 ENGLISH SENSORS...
Page 120: ...REFERENCES PAGE 120 ENGLISH SENSORS...