Installation instruction
For installation, please review the items below:
• Is the connected units quantity and the total capacity in the allowable range?
• Is the refrigerant pipe length in the limited range?
• Is the pipe size proper? And if the pipe installed horizontally?
• Is the branch pipe installed horizontally or vertically?
• Is the additional refrigerant counted correctly and weighed by the standard balance?
• Is there refrigerant leakage?
• Is all the indoor power supplies can be on/off simultaneously?
• Is the power voltage in compliance with the data marked on the rating label?
• Is the address of indoors has been set?
(1) Before installation
1) Before installation, check if the model, power supply, pipe, wires and parts purchased
respectively are correct.
2) Check if the indoors and outdoors can be combined as the following.
Outdoor
Indoor
Capacity(X 100W)
Indoor Qty
Total indoor capacity(X 100W)
AV08NMSETA
13
113~293
AV10NMSETA
16
140~364
AV12NMSETA
19
167~436